Pepperl Fuchs ICA-8DIO-CB10-IO
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Modules |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can ICA-8DIO-CB10-IO be shipped?
ICA-8DIO-CB10-IO is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up ICA-8DIO-CB10-IO in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for ICA-8DIO-CB10-IO and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for ICA-8DIO-CB10-IO, subject to availability and destination.
IO-Link printed circuit board module. I/O hub with IO-Link interface. LED PWR: LED green: flashing with short break (1 Hz) - IO-Link mode. LED OL: overload of sensor power supply; LED red. LED IO: Switching status/overload (input/output); 8 LED yellow/redyellow: input/output activered: output overload. Operating voltage: 18 ... 30 V DC, PELV. No-load supply current: max. 25 mA. Operating current: max. 2 A. Protection class: III. Interface type: IO-Link. IO-Link revision: 1.1. Device profile: Identification and Diagnosis - I&D. Process data: Inputs 2 Byte - Input signals 8 Bit - diagnosis signals 4 Bit Outputs 2 Byte - Output signals 8 Bit - Special functions 8 Bit. Vendor ID: 1 (0x0001). Device ID: 984577 (0x0F0601). Data transfer rate: COM3 (230.4 kbits/s). Min. cycle time: 1 ms. SIO mode support: no. Compatible master port type: Class A , Class B. Number/Type: 8 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO8). Supply: from IO-Link. Voltage: 18 ... 30 V. Current loading capacity: 400 mA , overload and short-circuit protected. Input current: ≤ 5 mA (limited internally). Switching point: Type 1 according to IEC 61131-2. Number/Type: 8 electronic outputs, PNP (IO1 … IO8), overload proof and short-circuit proof. Supply: from IO-Link. Voltage: ≥ (UB - 1.5 V). Current: 200 mA per output. Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013 EN 55011:2016: . Directive 2014/30/EU: EN 61326-1:2013 EN 55011:2016. Degree of protection: EN 60529:2000. Fieldbus standard: EN 61131-9:2013. Input: EN 61131-2:2007. Communication interface: IEC 61131-9 / IO-Link V1.1.3. Emitted interference: EN 61000-6-4:2007. Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006. UL approval: Protection class IP20 is not included in the UL approval. The protection class is tested by Pepperl+Fuchs.. Ambient temperature: -40 ... 70 °C (-40 ... 158 °F). Storage temperature: -40 ... 85 °C (-40 ... 185 °F). Relative humidity: 85 % non-condensing. Climatic conditions: For indoor use only. Altitude: ≤ 5000 m above MSL. Shock and impact resistance: 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks. Vibration resistance: 0.35 mm / 5 g 5 ... 500 Hz. Pollution degree: 2. Degree of protection: IP20 according to EN 60529. Connection: 200 mm, PVC cable 0.5 mm2. Material: . HousingPolyamide hot-melt adhesive: . Housing: Polyamide hot-melt adhesive. Mass: 33 g. Dimensions: . Height10 mmWidth36 mmLength39.5 mm: . Height: 10 mm. Width: 36 mm. Length: 39.5 mm. Note: This device is maintenance-free. If the device is used in a manner not specified by the manufaturer, the protection provided by the device may be impaired.
Specifications
Indicators/operating means
| LED PWR | LED green: flashing with short break (1 Hz) - IO-Link mode |
| LED OL | overload of sensor power supply; LED red |
| LED IO | Switching status/overload (input/output); 8 LED yellow/redyellow: input/output activered: output overload |
Electrical specifications
| Operating voltage | 18 ... 30 V DC, PELV UB |
| No-load supply current | max. 25 mA I0 |
| Operating current | max. 2 A IB |
| Protection class | III |
Interface
| Interface type | IO-Link |
| IO-Link revision | 1.1 |
| Device profile | Identification and Diagnosis - I&D |
| Process data | Inputs 2 Byte - Input signals 8 Bit - diagnosis signals 4 Bit Outputs 2 Byte - Output signals 8 Bit - Special functions 8 Bit |
| Vendor ID | 1 (0x0001) |
| Device ID | 984577 (0x0F0601) |
| Data transfer rate | COM3 (230.4 kbits/s) |
| Min. cycle time | 1 ms |
| SIO mode support | no |
| Compatible master port type | Class A , Class B |
Input
| Number/Type | 8 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO8) |
| Supply | from IO-Link |
| Voltage | 18 ... 30 V |
| Current loading capacity | 400 mA , overload and short-circuit protected |
| Input current | ≤ 5 mA (limited internally) |
| Switching point | Type 1 according to IEC 61131-2 |
Output
| Number/Type | 8 electronic outputs, PNP (IO1 … IO8), overload proof and short-circuit proof |
| Supply | from IO-Link |
| Voltage | ≥ (UB - 1.5 V) |
| Current | 200 mA per output |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 61326-1:2013 EN 55011:2016 | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 61326-1:2013 EN 55011:2016 |
Standard conformity
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 61131-9:2013 |
| Input | EN 61131-2:2007 |
| Communication interface | IEC 61131-9 / IO-Link V1.1.3 |
| Emitted interference | EN 61000-6-4:2007 |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006 |
Approvals and certificates
| UL approval | Protection class IP20 is not included in the UL approval. The protection class is tested by Pepperl+Fuchs. |
Ambient conditions
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity | 85 % non-condensing |
| Climatic conditions | For indoor use only |
| Altitude | ≤ 5000 m above MSL |
| Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Vibration resistance | 0.35 mm / 5 g 5 ... 500 Hz |
| Pollution degree | 2 |
Mechanical specifications
| Degree of protection | IP20 according to EN 60529 |
| Connection | 200 mm, PVC cable 0.5 mm2 |
| Material | |
| HousingPolyamide hot-melt adhesive | Housing |
| Housing | Polyamide hot-melt adhesive |
| Mass | 33 g |
| Dimensions | |
| Height10 mmWidth36 mmLength39.5 mm | Height |
| Height | 10 mm |
| Width | 36 mm |
| Length | 39.5 mm |
| Note | This device is maintenance-free. If the device is used in a manner not specified by the manufaturer, the protection provided by the device may be impaired. |
More Pepperl Fuchs parts
NewPepperl + Fuchs KFD2-GUT-EX1.D New open box
Available on requestPepperl Fuchs V19-W-BK15M-PUR-U-V19-G
Available on requestPepperl Fuchs V1SD-G-GN65M-PUR-E1S-V45-G