B&R X20AO2438 – I/O module, 2 analog outputs 4 to 20 mA
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Analog outputs |
| Lifecycle | Active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Datasheet | Manufacturer datasheet ↗ |
Shipping & availability
When can X20AO2438 be shipped?
X20AO2438 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up X20AO2438 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for X20AO2438 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20AO2438, subject to availability and destination.
• 2 analog current outputs
• HART protocol integration
• Support for HART variables
• Electrically isolated analog channels
• 16-bit digital converter resolution
• OSP mode
• NetTime timestamp: HART image
The module is equipped with 2 current outputs with 16-bit digital converter resolution. It supports the HART communication standard for data transfer, parameter configuration and diagnostics.
The 2 channels are electrically isolated from each other. The user can select between the 3 output ranges 4 to 20 mA , 0 to 20 mA and 0 to 24 mA .
Accessories
Required accessories (order separately)
| X20BM15 | Bus modules — The bus module is the base for all X20 24 VDC I/O modules; The internal I/O supply is interconnected; Manual node number assignment; Indepe… |
| X20BM11 | Bus modules — Bus module for 24 VDC I/O modules; The internal I/O power supply is connected through. The bus module is the base for all 24 VDC I/O module… |
| X20TB12 | Terminal blocks — Tool-free wiring with push-in technology; Simple wire release using lever; Ability to label each terminal; Plain text labeling also possibl… |
Specifications
Short description
| I/O module | 2 analog outputs 4 to 20 mA, 0 to 20 mA or 0 to 24 mA |
General information
| Diagnostics – Module run/error | Yes, using LED status indicator and software |
| Diagnostics – Outputs | Yes, using LED status indicator and software |
| Diagnostics – HART link | Yes, using LED status indicator and software |
| Diagnostics – HART error | Yes, using LED status indicator and software |
| Power consumption – Bus | 0.05 W |
| Power consumption – Internal I/O | 1.65 W |
| Certifications – CE | Yes |
| Certifications – UKCA | Yes |
| Certifications – CRA (Cyber Resilience Act) | In preparation |
| Certifications – ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X |
| Certifications – UL | cULus E115267; Industrial control equipment |
| Certifications – HazLoc | cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5 |
| Certifications – DNV | Temperature: B (0 to 55°C); Humidity: B (up to 100%); Vibration: B (4 g); EMC: B (bridge and open deck) |
| Certifications – CCS | Yes |
| Certifications – LR | ENV1 |
| Certifications – KR | Yes |
| Certifications – ABS | Yes |
| Certifications – BV | EC33B ; Temperature: 5 - 55°C; Vibration: 4 g; EMC: Bridge and open deck |
| Certifications – KC | Yes |
| B&R ID code | 0xB3AA |
| Status indicators | I/O function per channel, operating state, module status, HART |
| Additional power dissipation caused by actuators (resistive) [W] | - |
Analog outputs
| Data output rate – With HART | 210 ms (default) |
| Data output rate – Analog | 1 ms without ramp |
| Max. error " data-placement="top" data-html="true" data-container="body" data-content="At 25°C"> – 4 to 20 mA | ±0.025% " data-placement="top" data-html="true" data-container="body" data-content="Based on the current output value."> |
| Max. error " data-placement="top" data-html="true" data-container="body" data-content="At 25°C"> – 0 to 20 mA | ±0.022% " data-placement="top" data-html="true" data-container="body" data-content="Based on the current output value."> |
| Max. error " data-placement="top" data-html="true" data-container="body" data-content="At 25°C"> – 0 to 24 mA | ±0.02% " data-placement="top" data-html="true" data-container="body" data-content="Based on the current output value."> |
| Max. error " data-placement="top" data-html="true" data-container="body" data-content="At 25°C"> – 4 to 20 mA | ±0.025% " data-placement="top" data-html="true" data-container="body" data-content="Based on the respective output range."> |
| Max. error " data-placement="top" data-html="true" data-container="body" data-content="At 25°C"> – 0 to 20 mA | ±0.022% " data-placement="top" data-html="true" data-container="body" data-content="Based on the respective output range."> |
| Max. error " data-placement="top" data-html="true" data-container="body" data-content="At 25°C"> – 0 to 24 mA | ±0.02% " data-placement="top" data-html="true" data-container="body" data-content="Based on the respective output range."> |
| Output format – 4 to 20 mA | INT 0x0000 to 0x7FFF / 1 LSB = 0x0001 = 488.281 nA |
| Output format – 0 to 20 mA | INT 0x0000 to 0x7FFF / 1 LSB = 0x0001 = 610.352 nA ; UINT 0x0000 to 0xFFFF / 1 LSB = 0x0001 = 305.176 nA |
| Output format – 0 to 24 mA | INT 0x0000 to 0x5DC0 / 1 LSB = 0x0001 = 1000 nA |
| Max. gain drift – 4 to 20 mA | ±0.0055%/°C " data-placement="top" data-html="true" data-container="body" data-content="Based on the current output value."> |
| Max. gain drift – 0 to 20 mA | ±0.005%/°C " data-placement="top" data-html="true" data-container="body" data-content="Based on the current output value."> |
| Max. gain drift – 0 to 24 mA | ±0.005%/°C " data-placement="top" data-html="true" data-container="body" data-content="Based on the current output value."> |
| Max. offset drift – 4 to 20 mA | ±0.0035%/°C " data-placement="top" data-html="true" data-container="body" data-content="Based on the respective output range."> |
| Max. offset drift – 0 to 20 mA | ±0.002%/°C " data-placement="top" data-html="true" data-container="body" data-content="Based on the respective output range."> |
| Max. offset drift – 0 to 24 mA | ±0.002%/°C " data-placement="top" data-html="true" data-container="body" data-content="Based on the respective output range."> |
| Error caused by load change " data-placement="top" data-html="true" data-container="body" data-content="Load change from 1 Ω → 600 Ω, resistive"> – 4 to 20 mA | 0.14% |
| Error caused by load change " data-placement="top" data-html="true" data-container="body" data-content="Load change from 1 Ω → 600 Ω, resistive"> – 0 to 20 mA | 0.1% |
| Error caused by load change " data-placement="top" data-html="true" data-container="body" data-content="Load change from 1 Ω → 600 Ω, resistive"> – 0 to 24 mA | 0.1% |
| Test voltage – Channel - Channel | 1000 VAC |
| Test voltage – Channel - Bus | 1000 VAC |
| Test voltage – Channel - Ground | 1000 VAC |
| Output | 4 to 20 mA, 0 to 20 mA or 0 to 24 mA configurable using software |
| Digital converter resolution | 16-bit |
| Settling time on output change over entire range | 2 ms to 20 s, configurable using software |
| Output protection | Short-circuit proof, overvoltage protection (up to 30 VDC) |
| Open-circuit detection | Yes, using hardware and software |
| Data format | INT |
| Load per channel | Max. 600 Ω |
| Short-circuit proof | Yes, continuous |
| Output filter | Active second-order low-pass filter / Cutoff frequency 19 Hz; Configurable slew rate |
| Nonlinearity | <0.003% " data-placement="top" data-html="true" data-container="body" data-content="Based on the entire output range."> |
HART
| Multi-drop operation – Possible | Yes |
| Multi-drop operation – Stations | Up to 15 |
| Transmission amplitude – Minimum | 400 mV pp |
| Transmission amplitude – Typical | 500 mV pp |
| Transmission amplitude – Maximum | 600 mV pp |
| Receiving amplitude – Minimum | 120 mV pp |
| Receiving amplitude – Maximum | 1500 mV pp |
| Transfer rate | 1200 bit/s |
| Operating frequencies | 1200 Hz / 2200 Hz |
| Burst operation possible | Yes |
Electrical properties
| Electrical isolation | Channel isolated from channel and bus |
Operating conditions
| Mounting orientation – Horizontal | Yes |
| Mounting orientation – Vertical | Yes |
| Installation elevation above sea level – 0 to 2000 m | No limitation |
| Installation elevation above sea level – >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature – Horizontal mounting orientation | -25 to 60°C |
| Temperature – Vertical mounting orientation | -25 to 50°C |
| Temperature – Derating | See section "Derating". |
| Temperature – Storage | -40 to 85°C |
| Temperature – Transport | -40 to 85°C |
| Relative humidity – Operation | 5 to 95%, non-condensing |
| Relative humidity – Storage | 5 to 95%, non-condensing |
| Relative humidity – Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order 1x terminal block X20TB12 separately. ; Order 1x bus module X20BM11 separately. |
| Pitch | 12.5 +0.2 mm |
Downloads & documentation
Official documents from B&R, downloaded directly from the manufacturer.
Data sheets & manuals
| Datasheet X20(c)AO2438 | PDF · 2 MB · 1.51 (05/26/2025) - EN |
| X20 Package leaflet ATEX/CSA | PDF · 2 MB · 1.4 (09/17/2024) |
| X20 System User´s Manual | PDF · 50 MB · 4.40 (03/10/2026) - EN |
CAD & dimension drawings
| 3D File DXF/STEP X20 Electronic module | ZIP · 10 KB · 1.0 (10/17/2005) |
| 3D File STEP X20 I/O-Slice | ZIP · 872 KB · 1.1 (03/13/2019) |
| Dimensions PDF X20 Electronic module | PDF · 3 KB · 1.0 (10/17/2005) |
Certificates (15)
More B&R parts
Available on requestB&R X20AI8321 – I/O module, 8 analog inputs 0 to 20 mA / 4 to 20 mA
Available on requestB&R X20AIA744 – I/O module, 2 full-bridge strain gauge inputs
Available on requestB&R X20AIB744 – I/O module, 4 full-bridge strain gauge inputs
Available on requestB&R X20AO2437 – I/O module, 2 analog outputs 4 to 20 mA
Available on requestB&R X20AO2622 – I/O module, 2 analog outputs ±10 V or 0 to 20 mA / 4 to 20…
Available on requestB&R X20AO2632 – I/O module, 2 analog outputs ±10 V or 0 to 20 mA
Available on requestB&R X20AO2632-1 – I/O module, 2 analog outputs ±11 V or 0 to 22 mA
Available on requestB&R X20AO4622 – I/O module, 4 analog outputs ±10 V or 0 to 20 mA / 4 to 20…