Isolation amplifier; Current input signal; Current and voltage output signal; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²
Passive isolator, 1-channel; Current input signal; Current output signal; Power via input; 6 mm module width; 2,50 mm²
Short description:
WAGO's passive isolator (1‐channel) electrically isolates and filters 0(4) … 20 mA standard analog signals, while drawing power for signal transmission from the input circuit. The connected sensor supplies the passive isolator with the required power to energize the connected load.
Features:
No additional supply voltage required
3-way electrical isolation with 2.5 kV test voltage
| Safety Information | Outputs must not be left open! |
| Note | Use shielded signal cables!Only use shielded signal cables for analog input and output signals.This ensures the device maintains its specified accuracy and immunity to interference, even when external disturbances affect the signal cable. |
| Configuration options | Pre-configured |
| Input signal type | Current, Current |
| Input signal (current) | 0 … 20 mA, 4 … 20 mA |
| Input current (max.) | 40 mA |
| Input voltage (max.) | 20 V |
| Response threshold | 200 µA |
| Output signal type | Current, Current |
| Output signal (current) | 0 … 20 mA, 4 … 20 mA |
| Load impedance (current output) | ≤ 600 Ω Temperature range restrictions may occur. |
| Voltage drop | ≤ 2.5 V (at 20 mA at the output) |
| Limit frequency | 100 Hz |
| Step response (typ.) | 3.5 ms |
| Transmission error (typ.) | ≤ 0.1 % of upper-range value |
| Load error | ≤ 0.05 % of upper-range value; per 100 Ω load |
| Temperature coefficient | ≤ 0.01 %/K |
| Power supply type | Passive (via input) |
| Rated voltage | 300 V |
| Measurement category per EN/UL 61010-2-030 | CAT II (input) |
| Overvoltage category | II |
| Pollution degree | 2 |
| Protection type | IP20 |
| Test voltage (input/output) | AC 3 kV; 50 Hz; 1 min |
| Insulation type (input/analog output) | Reinforced insulation (safe isolation) |
| Connection technology | Push-in CAGE CLAMP® |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Fine-stranded conductor | 0.34 … 2.5 mm² / 22 … 14 AWG |
| Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
| Cable type | Shielded cable |
| Width | 6 mm / 0.236 inches |
| Height | 94 mm / 3.701 inches |
| Depth from upper-edge of DIN-rail | 97.8 mm / 3.85 inches |
| Mounting type | DIN-35 rail, DIN-35 rail |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 0.363 MJ |
| Weight | 24.7 g |
| Ambient temperature (operation) | -25 … +70 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Temperature range of connection cable | ≥ (Tambient + 15 K) |
| Temperature range of the connection cable (UL) | 70 °C |
| Relative humidity | 5 … 95 % (no condensation permissible) |
| Operating altitude (max.) | 2000 m |
| Conformity marking | CE |
| EMC immunity to interference | EN 61000-6-2 |
| EMC emission of interference | EN 61000-6-3 |
| Standards/specifications | EN 61010-1, DNV |
| Product Group | 6 (INTERFACE ELECTRONIC) |
| PU (SPU) | 1 pcs |
| Packaging type | Bag |
| Country of origin | DE |
| GTIN | 4045454471323 |
| Customs tariff number | 85437090300 |
| UNSPSC | 39121008 |
| eCl@ss 10.0 | 27-21-01-20 |
| eCl@ss 9.0 | 27-21-01-20 |
| ETIM 9.0 | EC002653 |
| ETIM 10.0 | EC002653 |
| ECCN | NO US CLASSIFICATION |
| RoHS Compliance Status | Compliant,No Exemption |
857-451 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 857-451 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 857-451, subject to availability and destination.

Isolation amplifier; Current input signal; Current and voltage output signal; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²

Isolation amplifier; Current and voltage input signal; 2 x current output signal; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²

Isolation amplifier; Current and voltage input signal; Supply voltage: 24 VDC; 6 mm module width

Loop-powered isolation amplifier; Bipolar current and voltage input signal; Current output signal; Configuration via DIP switch; Power supply via output; 6 mm module width; 2,50 mm²

Passive isolator, 2-channel; 2 x current input signal; 2 x current output signal; Power via input; 6 mm module width; 2,50 mm²

Frequency signal conditioner; Current and voltage output signal; Configuration via software; Supply voltage: 24 VDC; 6 mm module width

Threshold value switches; Analog values; 1 changeover contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²

Current signal conditioner; Current input signal; Current and voltage output signal; Digital output; Configuration via software; Supply voltage: 24 VDC; 6 mm module width; 2,50 mm²