Pepperl Fuchs VBA-4E4A-G2-ZA/EA2
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Modules |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can VBA-4E4A-G2-ZA/EA2 be shipped?
VBA-4E4A-G2-ZA/EA2 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up VBA-4E4A-G2-ZA/EA2 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for VBA-4E4A-G2-ZA/EA2 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VBA-4E4A-G2-ZA/EA2, subject to availability and destination.
AS-Interface sensor/actuator module. G2 flat module, 4 inputs (PNP) and 4 electronic outputs. Node type: A/B node. AS-Interface specification: V3.0. Required gateway specification: ≥ V3.0. Profile: S-7.A.E. IO code7ID codeAID1 code7ID2 codeE: . IO code: 7. ID code: A. ID1 code: 7. ID2 code: E. UL File Number: E223772. LED FAULT: error display; LED redred: communication error or address is 0red flashing: overload of sensor power supply or outputs. LED PWR: AS-Interface voltage; LED green. LED AUX: ext. auxiliary voltage UAUX ; LED green. LED IN: switching state (input); 4 LED yellow. LED OUT: Switching state (output); 4 LED yellow. Auxiliary voltage (output): 20 ... 30 V DC PELV. Rated operating voltage: 26.5 ... 31.6 V from AS-Interface. Rated operating current: ≤ 40 mA (without sensors) / max. 220 mA. Protection class: III. Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV). Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC. Supply: from AS-Interface. Voltage: 21 ... 31 V. Current loading capacity: ≤ 180 mA (TB ≤ 40 °C),≤ 140 mA (TB ≤ 60 °C), , overload and short-circuit protected. Input current: ≤ 9 mA (limited internally). Switching point: according to DIN EN 61131-2 (Type 2). 0 (unattenuated)≤ 3 mA1 (attenuated)≥ 5 mA: . 0 (unattenuated): ≤ 3 mA. 1 (attenuated): ≥ 5 mA. Signal delay: < 2 ms (input/AS-Interface). Signal frequency: ≤ 250 Hz. Number/Type: 4 electronic outputs, PNP, overload and short-circuit proof. Supply: from external auxiliary voltage UAUX. Voltage: ≥ (UAUX - 0.5 V). Current: 0.5 A per output , 2 A total. Electromagnetic compatibility: . Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001: . Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001. Degree of protection: EN 60529:2000. Fieldbus standard: EN 62026-2:2013. Input: EN 61131-2:2007. Emitted interference: EN 61000-6-4:2001. AS-Interface: EN 62026-2:2013. Noise immunity: EN 61000-6-2:2001. Ambient temperature: -25 ... 60 °C (-13 ... 140 °F). Storage temperature: -25 ... 85 °C (-13 ... 185 °F). Relative humidity: 85 % , noncondensing. Climatic conditions: For indoor use only. Altitude: ≤ 2000 m above MSL. Pollution degree: 3. Degree of protection: IP67. Connection: Cable piercing methodflat cable yellow/flat cable blackinputs/outputs: M12 round connector. Material: . HousingPBT: . Housing: PBT. Mass: 150 g. Tightening torque, cable gland: 0.4 Nm. Mounting: Mounting plate
Specifications
General specifications
| Node type | A/B node |
| AS-Interface specification | V3.0 |
| Required gateway specification | ≥ V3.0 |
| Profile | S-7.A.E |
| IO code7ID codeAID1 code7ID2 codeE | IO code |
| IO code | 7 |
| ID code | A |
| ID1 code | 7 |
| ID2 code | E |
| UL File Number | E223772 |
Indicators/operating means
| LED FAULT | error display; LED redred: communication error or address is 0red flashing: overload of sensor power supply or outputs |
| LED PWR | AS-Interface voltage; LED green |
| LED AUX | ext. auxiliary voltage UAUX ; LED green |
| LED IN | switching state (input); 4 LED yellow |
| LED OUT | Switching state (output); 4 LED yellow |
Electrical specifications
| Auxiliary voltage (output) | 20 ... 30 V DC PELV UAUX |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface Ue |
| Rated operating current | ≤ 40 mA (without sensors) / max. 220 mA Ie |
| Protection class | III |
| Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
| Supply | from AS-Interface |
| Voltage | 21 ... 31 V |
| Current loading capacity | ≤ 180 mA (TB ≤ 40 °C),≤ 140 mA (TB ≤ 60 °C), , overload and short-circuit protected |
| Input current | ≤ 9 mA (limited internally) |
| Switching point | according to DIN EN 61131-2 (Type 2) |
| 0 (unattenuated)≤ 3 mA1 (attenuated)≥ 5 mA | 0 (unattenuated) |
| 0 (unattenuated) | ≤ 3 mA |
| 1 (attenuated) | ≥ 5 mA |
| Signal delay | < 2 ms (input/AS-Interface) |
| Signal frequency | ≤ 250 Hz |
Output
| Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
| Supply | from external auxiliary voltage UAUX |
| Voltage | ≥ (UAUX - 0.5 V) |
| Current | 0.5 A per output , 2 A total |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001 | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001 |
Standard conformity
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 62026-2:2013 |
| Input | EN 61131-2:2007 |
| Emitted interference | EN 61000-6-4:2001 |
| AS-Interface | EN 62026-2:2013 |
| Noise immunity | EN 61000-6-2:2001 |
Ambient conditions
| Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity | 85 % , noncondensing |
| Climatic conditions | For indoor use only |
| Altitude | ≤ 2000 m above MSL |
| Pollution degree | 3 |
Mechanical specifications
| Degree of protection | IP67 |
| Connection | Cable piercing methodflat cable yellow/flat cable blackinputs/outputs: M12 round connector |
| Material | |
| HousingPBT | Housing |
| Housing | PBT |
| Mass | 150 g |
| Tightening torque, cable gland | 0.4 Nm |
| Mounting | Mounting plate |
More Pepperl Fuchs parts
NewPepperl + Fuchs KFD2-GUT-EX1.D New open box
Available on requestPepperl Fuchs V19-W-BK15M-PUR-U-V19-G