IFM PV8023
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | All pressure sensors / vacuum sensors |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can PV8023 be shipped?
PV8023 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up PV8023 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for PV8023 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for PV8023, subject to availability and destination.
Compact housing for use where space is restricted Very high overpressure and vacuum resistance Robust stainless steel housing with high shock and vibration resistance Two programmable switching outputs, one of them with IO-Link communication interface Integrated temperature measurement via IO-Link User-friendly communication and parameterisation via IO-Link
Specifications
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range | 0...60 bar; 0...870 psi; 0...6 MPa |
| 0...60 bar | 0...870 psi |
| Process connection | threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5 |
Application
| Measuring element | metallic thin film cell |
| Application | for industrial applications |
| Media | liquids and gases |
| Medium temperature[°C] [°C] | -40...90 |
| Min. burst pressure | 900 bar; 13050 psi; 90 MPa |
| 900 bar | 13050 psi |
| Pressure rating | 150 bar; 2175 psi; 15 MPa |
| 150 bar | 2175 psi |
| Note on pressure rating | static |
| Vacuum resistance | -1000 mbar; -0.1 MPa |
| -1000 mbar | -0.1 MPa |
| Type of pressure | relative pressure |
Electrical data
| Operating voltage[V] [V] | 18...30 DC |
| Current consumption[mA] [mA] | < 15 |
| Min. insulation resistance[MΩ] [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time[s] [s] | < 0.3 |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2 |
Outputs
| Total number of outputs | 2 |
| Output signal | switching signal; IO-Link; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC[V] [V] | 2 |
| Permanent current rating of switching output DC[mA] [mA] | 100 |
| Switching frequency DC[Hz] [Hz] | < 130 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Measuring range | -40...90 °C; -40...194 °F |
| 0...60 bar | 0...870 psi |
| Set point SP | -38...90 °C; -36.4...194 °F |
| 0.6...60 bar | 9...870 psi |
| Reset point rP | -40...88 °C; -40...190.4 °F |
| 0.31...59.71 bar | 4...866 psi |
| In steps of | 0.1 °C; 0.1 °F |
| 0.01 bar | 1 psi |
| Factory setting | SP1 = 15 bar; rP1 = 13.8 bar; ou1 = Hno;; SP2 = 45 bar; rP2 = 43.8 bar; ou2 = Hno;; dS1/dS2 = 0 ms; dr1/dr2 = 0 ms; coF = 0 %; P-n = PnP; dAP= 60 ms |
| SP1 = 15 bar | rP1 = 13.8 bar |
| SP2 = 45 bar | rP2 = 43.8 bar |
| dS1/dS2 = 0 ms | dr1/dr2 = 0 ms |
| coF = 0 % | P-n = PnP |
| -40...90 °C | -40...194 °F |
| -38...90 °C | -36.4...194 °F |
| -40...88 °C | -40...190.4 °F |
| 0.1 °C | 0.1 °F |
Accuracy / deviations
| Switch point accuracy[% of the span] [% of the span] | < ± 0,5 (nach DIN EN 61298-2) |
| Repeatability[% of the span] [% of the span] | < ± 0,05; (with temperature fluctuations < 10 K) |
| Characteristics deviation[% of the span] [% of the span] | < ± 0,5; (linearity incl. hysteresis and repeatability, limit value setting to DIN EN IEC 62828-1) |
| Linearity deviation[% of the span] [% of the span] | < ± 0,1 (BFSL) / < ± 0,2 (LS) |
| Hysteresis deviation[% of the span] [% of the span] | < ± 0,2 |
| Long-term stability[% of the span] [% of the span] | < ± 0,1; (per 6 months) |
| Temperature coefficient zero point[% of the span / 10 K] [% of the span / 10 K] | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) |
| Temperature coefficient span[% of the span / 10 K] [% of the span / 10 K] | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) |
| Accuracy[K] [K] | ± 2 K + (0.1 x (ambient temperature - medium temperature)) |
| Notes on the accuracy / deviation | temperature range -10 to 80 °C |
Response times
| Response time[ms] [ms] | < 3 |
| Dynamic response T05 / T09[s] [s] | < 80 / < 210 ( under ifm reference conditions ) |
Software / programming
| Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping |
Interfaces
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Common - I&D; Identification and Diagnosis; Function; Measurement data, standard resolution |
| Common - I&D | Identification and Diagnosis |
| Function | Measurement data, standard resolution |
| SIO mode | yes |
| Required master port type | A |
| Process data analogue | 5 |
| Process data binary | 2 |
| Min. process cycle time[ms] [ms] | 4.5 |
| IO-Link resolution pressure[bar] [bar] | 0.02 |
| IO-Link resolution temperature[K] [K] | 0.2 |
| IO-Link process data (cyclical) | pressure; 16; temperature; 16; device status; 4; binary switching information; 2 |
| pressure | 16 |
| temperature | 16 |
| device status | 4 |
| binary switching information | 2 |
| IO-Link functions (acyclical) | application specific tag; internal temperature; operating hours counter; switching cycles counter; Pressure peak counter; Temperature peak counter |
| Supported DeviceIDs | default; 1215 |
| default | 1215 |
Operating conditions
| Ambient temperature[°C] [°C] | -40...90 |
| Storage temperature[°C] [°C] | -40...100 |
| Protection | IP 67; IP 69K |
Tests / approvals
| EMC | DIN EN 61326-1 |
| Shock resistance | DIN EN 60068-2-27; 500 g (1 ms) |
| DIN EN 60068-2-27 | 500 g (1 ms) |
| Vibration resistance | DIN EN 60068-2-6; 20 g (10...2000 Hz) |
| DIN EN 60068-2-6 | 20 g (10...2000 Hz) |
| MTTF[years] [years] | 668 |
| UL approval | UL approval no.; J037; File number UL; E174189 |
| UL approval no. | J037 |
| File number UL | E174189 |
| Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data
| Weight[g] [g] | 56.1 |
| Housing | cylindrical |
| Dimensions[mm] [mm] | Ø 19 / L = 66 |
| Materials | stainless steel (630/1.4542/17-4 PH); stainless steel (316L/1.4404); PEI |
| Materials (wetted parts) | stainless steel (303/1.4305); stainless steel (630/1.4542/17-4 PH) |
| Min. pressure cycles | 60 million; (at 1.2 times nominal pressure) |
| Tightening torque[Nm] [Nm] | 25...35; (recommended tightening torque; depends on the lubrication, the seal and the pressure load) |
| Process connection | threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5 |
| Process connection sealing | FKM (DIN EN ISO 1179-2) |
| Restrictor element integrated | yes |
Remarks
| Remarks | BFSL = Best Fit Straight Line; LS = limit value setting |
| Pack quantity | 1 pcs. |
Electrical connection
| Connector | 1 x M12; coding: A |