Isolation amplifier; Bipolar current and voltage input signal; Bipolar current and voltage output signal; Digital output; Supply voltage: 24 VDC; 12.5 mm module width
Temperature signal conditioner; Current and voltage output signal; Configuration via software; Supply voltage: 24 VDC
Short description:
WAGO's RTD TC temperature signal conditioner for RTD sensors, potentiometers, resistors and thermocouples monitors and reports signals for up to two switching thresholds. The sensor and status information that is collected is also converted to a standard analog signal.
Features:
A relay with changeover contact reacts to configured measurement range limits (on/off switching delay and threshold value switch function can be configured with up to two threshold values).
Configurable Pt factor
Adjustable software filter
Input of customer-specific sensors via the interface configuration software
Safe 3-way isolation with 3 kV test voltage per EN 61010-1
Analog unipolar/bipolar signals (current/voltage) at output
Additional digital signal output for configured measurement range limits
Adjustable transfer characteristic
| Note | This product is powered by 24 VDC, which can be bridged using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is important to ensure that the maximum permissible total current of 1 A is not exceeded. |
| Configuration options | WAGO Interface Configuration Software |
| Input signal type | RTD sensors, Potentiometer, Resistance, TC sensors |
| Sensor types (RTD) | Pt10 … Pt2000 (expandable) |
| Sensor connection | 2-wire; 3-wire; 4-wire; differential; potentiometer |
| Sensor power supply (RTD) max. | ≤ 0.5 mA |
| Temperature measurement range (RTD) | −200 … +850 °C |
| Measurement span (RTD) min. | 50 K |
| Sensor types (TC) | Type J, Type K, Type E, Type R, Type N, Type S, Type T, Type B, Type C |
| Temperature measurement range (TC) | −200 … 1200 °C (Type J), −200 … 1372 °C (Type K), −200 … 1000 °C (Type E), 250 … 1768 °C (Type R), −200 … 1300 °C (Type N), −50 … 1664 °C (Type S), −200 … 400 °C (Type T), 250 … 1820 °C (Type B), 0 … 2320 °C (Type C) |
| Measurement span (TC) min. | 100 K |
| Cold junction compensation | ON/OFF (default: ON) |
| Cold junction error | 3 K (typ. 2 K ) |
| Input range (resistor) | 0 … 10 kΩ |
| Input range (potentiometer) | 0 … 10 kΩ |
| Measurement span (min.) | 50 Ω |
| Output signal type | Current, Voltage |
| Output signal (voltage) | ±12 V |
| Output signal (current) | ±24 mA |
| Load impedance (voltage output) | ≥ 2 kΩ |
| Load impedance (current output) | ≤ 600 Ω |
| Switching voltage (DO) max. | Applied supply voltage − 0.3 V |
| Continuous current (DO) max. | 100 mA (no internal restriction) |
| Number of switching thresholds (DO) | 1 or 2 (adjustable) |
| Configurable rise/fall delay time (DO) | 0 … 60 s (via software) |
| Dielectric strength (open contact) (AC, 1 min) | 1 kV<sub>eff</sub> |
| Number of changeover/switchover contacts | 1 |
| Switching Voltage, Max. | 250 VAC |
| Dielectric strength (open contact) (AC, 1 min) | 1 kVrms |
| Number of switching thresholds (relay) | 1 or 2 (adjustable) |
| Configurable rise/fall delay time (relay) | 0 … 60 s (via software) |
| Software filter (adjustable) | Moving average value (filter level: 30) |
| Step response (typ.) | 130 ms (2-wire), 700 ms (3-wire), 700 ms (4-wire), 600 ms (difference), 500 ms (potentiometer), 150 ms (cold junction compensation off), 400 ms (cold junction compensation on) |
| Transmission error (typ.) | ≤ 0.1 % at full measurement span |
| Transmission error for the set measurement range | ≤ (100 K/set measurement range [K]) % |
| Temperature coefficient | ≤ 0.01 %/K |
| Power supply type | 24 VDC |
| Nominal supply voltage U<sub>S</sub> | 24 VDC |
| Supply voltage range | -60 … +30 % |
| Current consumption at nominal supply voltage | ≤ 70 mA (+ IDO) |
| Rated voltage | 300 V |
| Rated voltage of the measurement circuit connections per EN 61010-2-030 | AC 300 V |
| Measurement category per EN/UL 61010-2-030 | CAT II (input) |
| Note on insulation parameters | The digital output (DO) operates at the supply potential. The service interface operates at the potential of the analog output. The DIN-rail contact (functional ground) is capacitively coupled to the analog output. |
| Protection type | IP20 |
| Test voltage (input/output/supply) | 3 kVAC; 50 Hz; 1 min |
| Test voltage (input/analog output/relay output/supply) | 3 kVAC; 50 … 60 Hz; 1 min |
| Test voltage (input/DIN-rail contact/relay output/supply) | 3 kVAC; 50 … 60 Hz; 1 min |
| Overvoltage category | II |
| Pollution degree | 2 |
| Insulation type (input/analog output/relay output/supply) | Reinforced insulation (safe isolation) |
| Insulation type (input/DIN-rail contact/relay output/supply) | Reinforced insulation (safe isolation) |
| Connection technology | Push-in CAGE CLAMP® |
| WAGO connector | picoMAX® 5.0 |
| Solid conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
| Fine-stranded conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
| Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
| Width | 22.5 mm / 0.886 inches |
| Height | 110 mm / 4.331 inches |
| Depth from upper-edge of DIN-rail | 107 mm / 4.213 inches |
| Mounting type | DIN-35 rail |
| Fire load | 2.158 MJ |
| Weight | 126.7 g |
| Pollution degree | 2 |
| Ambient temperature (operation) | -40 … +70 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Temperature range of connection cable | ≥ (Tambient + 10 K) |
| Temperature range of the connection cable (UL) | 85 °C |
| Relative humidity | 5 … 95 % (non-condensing) |
| Operating altitude (max.) | 2000 m |
| Conformity marking | CE |
| EMC immunity to interference | EN 61000-6-2; EN 61326-2-3 |
| EMC emission of interference | EN 61000-6-3; EN 61326-2-3 |
| Standards/specifications | EN 61010-1, EN 61373 |
| PU (SPU) | 1 pcs |
| Packaging type | bag |
| Country of origin | DE |
| GTIN | 4055143655507 |
| Customs tariff number | 85437090300 |
| UNSPSC | 41113630 |
| eCl@ss 10.0 | 27-21-01-29 |
| eCl@ss 9.0 | 27-21-01-29 |
| ETIM 9.0 | EC002919 |
| ETIM 10.0 | EC002919 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 1303-86-2, 1317-36-8, 7439-92-1, 75980-60-8, 79-94-7 |
| REACH Candidate List Substance | 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol, Diboron trioxide, Lead, Lead monoxide, Perfluorobutane sulfonic acid (PFBS) and its salts, Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)- |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I, 7(c)-II |
| SCIP notification number (Austria) | beac9352-aef0-42a2-b7f0-a83392390cff |
| SCIP notification number (Belgium) | eeb9df68-9e28-4e3e-92ac-8ef9ab87c305 |
| SCIP notification number (Bulgaria) | 61e19286-b116-40e0-90e0-0d98747b35c6 |
| SCIP notification number (Czech Republic) | ccfdefc9-f0b3-4620-b412-b6adce9425b4 |
| SCIP notification number (Denmark) | 1d7e7fd7-5fa4-47bb-96ed-30ae8a6161f6 |
| SCIP notification number (Finland) | 4e130f44-9148-4325-97d7-6d58f5d97835 |
| SCIP notification number (France) | 30e01dd3-5b6f-498f-9b37-54a0502b9f9e |
| SCIP notification number (Germany) | ef2b2ca0-d8d7-4e0c-81db-287ee7497471 |
| SCIP notification number (Hungary) | 93a905b5-7155-4b52-8695-61a9c5ddcc08 |
| SCIP notification number (Italy) | 7a1074e6-72fb-4fec-bfaa-c1cebf85968f |
| SCIP notification number (Netherlands) | e6753189-be82-47d8-93e5-8cabc3e2d142 |
| SCIP notification number (Poland) | 91684334-ada5-46cb-8352-31567b986a40 |
| SCIP notification number (Romania) | 9a8786ac-ee1e-477b-8851-a03a87e77e4a |
| SCIP notification number (Sweden) | b9aa1443-ef24-4f0e-a0f8-b04a5d1a7f4f |
2857-535 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 2857-535 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 2857-535, subject to availability and destination.

Isolation amplifier; Bipolar current and voltage input signal; Bipolar current and voltage output signal; Digital output; Supply voltage: 24 VDC; 12.5 mm module width

Threshold value switches; RTD sensors; 1 make contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 12.5 mm module width

Threshold value switches; RTD sensors; 1 make contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 12.5 mm module width; Railway

Threshold value switches; Thermocouples; 1 make contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 12.5 mm module width

Temperature signal conditioner; Configuration via software; Supply voltage: 24 VDC

Current signal conditioner; Current input signal; Current and voltage output signal; Digital and relay output; Configuration via software; Supply voltage: 24 VDC; 22.5 mm module width

Single-Phase Power Signal Conditioner; Current and voltage input signal; Current and voltage output signal; Digital output; Configuration via software; Supply voltage: 24 VDC

3-Phase Power Measurement Module; 3x277/480 V/RC; Modbus RTU; Digital output; Configuration via software; Supply voltage: 24 VDC