Pepperl Fuchs VBA-4E-KE5-IL
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Modules |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can VBA-4E-KE5-IL be shipped?
VBA-4E-KE5-IL is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up VBA-4E-KE5-IL in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for VBA-4E-KE5-IL and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VBA-4E-KE5-IL, subject to availability and destination.
AS-Interface analog module. Switch cabinet module, 4 analog Inputs. Node type: Standard node. AS-Interface specification: V3.0. Required gateway specification: ≥ V2.1. UL File Number: E223772. MTBF: 173 a. LED FAULT: Fault indication: red LEDRed: communication error or address is 0Red flashing: peripheral fault. LED PWR: AS-Interface voltage; green LEDGreen: voltage OKFlashing green: address 0 or peripheral error. LED AUX: ext. auxiliary voltage UAUX; dual LED green/redgreen: voltage OKred: reverse voltage. LED IN: status of input signal; LED yellowoff: not activeon: signal within measuring rangeflashing: signal outside of measuring range. Auxiliary voltage (output): 20 ... 30 V DC PELV. Rated operating voltage: 26.5 ... 31.6 V from AS-Interface. Rated operating current: ≤ 70 mA. Protection class: III. Current consumption: IAUX ≤ 650 mA. Surge protection: UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV). Number/Type: 4 analog inputsCurrent: 0 mA ... 20 mA/4 mA ... 20 mA. Supply: From auxiliary voltage UAUX. Current loading capacity: ≤ 600 mA From auxiliary voltage UAUX ; overload and short-circuit resistant. Input resistance: current input: max. 70 Ω. Accuracy: 0.1 % of input signal range at 25 °C (298 K). Resolution: 15 Bit. Temperature influence: 0.0025 %/K of input signal range. Temperature influence: 1 µA/K or 0,3 mV/K. Electromagnetic compatibility: . Directive 2014/30/EUEN 62026-2:2013: . Directive 2014/30/EU: EN 62026-2:2013. Degree of protection: EN 60529:2000. Fieldbus standard: EN 62026-2:2013. Emitted interference: EN 61000-6-4:2007. AS-Interface: EN 62026-2:2013. Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013. Profile: S-7.3.E. IO code: 7. ID code: 3. ID1 code: F. ID2 code: E. Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.. Parameter bits (programmable via AS-i): function. P050/60 Hz filterP0=1, enabledP0=0, disabledP1not usedP2Indication of the peripheral fault by exceeding measuring rangeP2=1, peripheral fault is reportedP2=0, peripheral fault is not reportedP3P3=1, wire break detection activeP3=0, wire break detection disabled: . P0: 50/60 Hz filterP0=1, enabledP0=0, disabled. P1: not used. P2: Indication of the peripheral fault by exceeding measuring rangeP2=1, peripheral fault is reportedP2=0, peripheral fault is not reported. P3: P3=1, wire break detection activeP3=0, wire break detection disabled. Ambient temperature: -25 ... 70 °C (-13 ... 158 °F). Storage temperature: -25 ... 85 °C (-13 ... 185 °F). Relative humidity: 85 % , noncondensing. Climatic conditions: For indoor use only. Altitude: ≤ 2000 m above MSL. Shock and impact resistance: 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks. Vibration resistance: 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles. Pollution degree: 2. Degree of protection: IP20. Connection: Removable push-in terminalsrated connection capacity:rigid: 0.20 mm2 ... 1.5 mm2flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2. Material: . HousingPA 66-FR: . Housing: PA 66-FR. Mass: 110 g. Dimensions: . Height100 mmWidth18.9 mmLength124 mm: . Height: 100 mm. Width: 18.9 mm. Length: 124 mm. Mounting: DIN mounting rail. Note: Max. length of jumpers = 5 cm
Specifications
General specifications
| Node type | Standard node |
| AS-Interface specification | V3.0 |
| Required gateway specification | ≥ V2.1 |
| UL File Number | E223772 |
| MTBF | 173 a |
Indicators/operating means
| LED FAULT | Fault indication: red LEDRed: communication error or address is 0Red flashing: peripheral fault |
| LED PWR | AS-Interface voltage; green LEDGreen: voltage OKFlashing green: address 0 or peripheral error |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/redgreen: voltage OKred: reverse voltage |
| LED IN | status of input signal; LED yellowoff: not activeon: signal within measuring rangeflashing: signal outside of measuring range |
Electrical specifications
| Auxiliary voltage (output) | 20 ... 30 V DC PELV UAUX |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface Ue |
| Rated operating current | ≤ 70 mA Ie |
| Protection class | III |
| Current consumption | IAUX ≤ 650 mA |
| Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
Input
| Number/Type | 4 analog inputsCurrent: 0 mA ... 20 mA/4 mA ... 20 mA |
| Supply | From auxiliary voltage UAUX |
| Current loading capacity | ≤ 600 mA From auxiliary voltage UAUX ; overload and short-circuit resistant |
| Input resistance | current input: max. 70 Ω |
| Accuracy | 0.1 % of input signal range at 25 °C (298 K) |
| Resolution | 15 Bit |
| Temperature influence | 0.0025 %/K of input signal range |
Output
| Temperature influence | 1 µA/K or 0,3 mV/K |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 62026-2:2013 | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 62026-2:2013 |
Standard conformity
| Degree of protection | EN 60529:2000 |
| Fieldbus standard | EN 62026-2:2013 |
| Emitted interference | EN 61000-6-4:2007 |
| AS-Interface | EN 62026-2:2013 |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
Programming instructions
| Profile | S-7.3.E |
| IO code | 7 |
| ID code | 3 |
| ID1 code | F |
| ID2 code | E |
| Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i) | function |
| P050/60 Hz filterP0=1, enabledP0=0, disabledP1not usedP2Indication of the peripheral fault by exceeding measuring rangeP2=1, peripheral fault is reportedP2=0, peripheral fault is not reportedP3P3=1, wire break detection activeP3=0, wire break detection disabled | P0 |
| P0 | 50/60 Hz filterP0=1, enabledP0=0, disabled |
| P1 | not used |
| P2 | Indication of the peripheral fault by exceeding measuring rangeP2=1, peripheral fault is reportedP2=0, peripheral fault is not reported |
| P3 | P3=1, wire break detection activeP3=0, wire break detection disabled |
Ambient conditions
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity | 85 % , noncondensing |
| Climatic conditions | For indoor use only |
| Altitude | ≤ 2000 m above MSL |
| Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree | 2 |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | Removable push-in terminalsrated connection capacity:rigid: 0.20 mm2 ... 1.5 mm2flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
| Material | |
| HousingPA 66-FR | Housing |
| Housing | PA 66-FR |
| Mass | 110 g |
| Dimensions | |
| Height100 mmWidth18.9 mmLength124 mm | Height |
| Height | 100 mm |
| Width | 18.9 mm |
| Length | 124 mm |
| Mounting | DIN mounting rail |
| Note | Max. length of jumpers = 5 cm |
More Pepperl Fuchs parts
NewPepperl + Fuchs KFD2-GUT-EX1.D New open box
Available on requestPepperl Fuchs V19-W-BK15M-PUR-U-V19-G
Available on requestPepperl Fuchs V1SD-G-GN65M-PUR-E1S-V45-G