Pepperl Fuchs HiD-ADP-HiC-DI
Adapter Set for HiD Termination Board
- MPN
- HiD-ADP-HiC-DI
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
- 100% positive eBay feedback
What is the Pepperl Fuchs HiD-ADP-HiC-DI?
Set consisting of isolated barrier HiC2822 and adapter HiD-ADP-HiC
2-channel isolated barrier
24 V DC supply (bus powered)
Dry contact or NAMUR inputs
2 relay contact outputs
For HiD Termination Board mounting
Up to SIL 2 acc. to IEC/EN 61508
Set consisting of isolated barrier HiC2822 and adapter HiD-ADP-HiC, 2-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 2 relay contact outputs, For HiD Termination Board mounting, Up to SIL 2 acc. to IEC/EN 61508, Signal type: Digital Input, Safety Integrity Level (SIL): SIL 2, Field device: NAMUR sensor, Type: 2 x relay (NO contact)
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 70188962 |
| Signal type | Digital Input |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 2 |
Supply
| Rated voltage | 19 ... 30 V DC bus powered via Termination Board Ur |
| Rated current | ≤ 30 mA Ir |
| Power dissipation | ≤ 600 mW |
| Power consumption | ≤ 600 mW |
Input
| Connection side | field side |
| Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.7 mA |
Output
| Connection side | control side |
| Output I | signal ; relay |
| Output II | signal ; relay |
Fault indication output
| Output type | open collector transistor (internal fault bus) |
Indicators/settings
| Display elements | LEDs |
| Control elements | DIP switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | see datasheet of isolated barrier |
Conformity
| Electromagnetic compatibility | see datasheet of isolated barrier |
| Degree of protection | IEC 60529 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Mass | approx. 200 g |
| Dimensions | 18 x 106 x 168 mm (0.7 x 4.2 x 6.6 inch) (W x H x D) |
| Mounting | on termination board |
Data for application in connection with hazardous areas
| EU-type examination certificate | see datasheet of isolated barrier |
International approvals
| UL approval | see datasheet of isolated barrier |
| IECEx approval: IECEx certificate | see datasheet of isolated barrier |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
HiD-ADP-HiC-DI: frequently asked questions
When can HiD-ADP-HiC-DI be shipped?
HiD-ADP-HiC-DI is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up HiD-ADP-HiC-DI in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for HiD-ADP-HiC-DI and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?