Pepperl Fuchs HiCTB16-TRX-RAS-PL-AI16
Termination Board
- MPN
- HiCTB16-TRX-RAS-PL-AI16
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
- 100% positive eBay feedback
What is the Pepperl Fuchs HiCTB16-TRX-RAS-PL-AI16?
System board for Schneider Electric, Tricon CX series by Triconex
For 32-channel (16+16) AI cards 3722X and 3723X
For 16 modules
Recommended modules: HiC2027 (AI), HiC2027ES (AI)
24 V DC supply
Hazardous area: pluggable screw terminals, blue
Non-hazardous area: screw terminals, black
Non-hazardous area: ELCO socket, 56-pin
Up to SIL 3 acc. to IEC/EN 61508
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2027 (AI), HiC2027ES (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: screw terminals, black, Non-hazardous area: ELCO socket, 56-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CX, Safety Integrity Level (SIL): SIL 3
Specifications
Functional safety related parameters
| Order code (Pepperl+Fuchs part number) | 70159655 |
| Safety Integrity Level (SIL) | SIL 3 |
| Systematic capability (SC) | SC 3 |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Supply
| Connection | X20: terminals 3, 5(+); 4, 6(-) |
| Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Ripple | ≤ 10 % |
| Fusing | 4 A , in each case for 16 modules |
| Power dissipation | ≤ 500 mW , without modules |
| Reverse polarity protection | yes |
Redundancy
| Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
Fault indication output
| Connection | X20: terminals 1(+), 2(-) |
| Output type | volt-free transistor output , not short-circuit protected , not overload protected |
| Rated voltage | 30 V DC Ur |
| Rated current | 100 mA Ir |
| Signal level | no fault: (external voltage) - 1 V max. for 100 mA (Tamb = 25 °C (77 °F)) power supply fault/module fault: blocked output (off-state current ≤ 10 µA) |
Indicators/settings
| Display elements | LED PWR1 (termination board power supply), green LED LED PWR2 (termination board power supply), green LED |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Electromagnetic compatibility | EN IEC 61326-3-2:2018 , NE 21:2017 For further information see system description. |
| Degree of protection | IEC 60529:2001 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection: Field side | explosion hazardous area: pluggable screw terminals , blue |
| Connection: Control side | non-explosion hazardous area: output I: ELCO socket, 56-pin output II: screw terminals , black |
| Connection: Supply | pluggable screw terminals , black |
| Connection: Fault output | pluggable screw terminals , black |
| Core cross section | screw terminals 0.25 ... 2.5 mm2 (24 ... 12 AWG) |
| Material | housing: polycarbonate, 10 % glass fiber reinforced |
| Mass | approx. 1000 g |
| Dimensions | 266 x 200 x 163 mm (10.5 x 7.9 x 6.42 inch) (W x H x D) , depth including module assembly |
| Height | 200 mm |
| Width | 266 mm |
| Depth | 163 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | CESI 06 ATEX 022 |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Non-hazardous area: Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) |
| Galvanic isolation: Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000 |
International approvals
| UL approval | E106378 |
| Control drawing | 116-0327 |
| IECEx approval: IECEx certificate | IECEx CES 06.0003 |
| IECEx approval: IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
Certificates (5)
- EU Declaration of Conformity (Pepperl+Fuchs)
- South Africa MASC (MASC MS/17-0855)
- Brasil TUV Rheinland Brazil (TÜV 14.0084 X)
- Europe CESI ATEX Category (1) GD ATEX Category (M1) (CESI 06 ATEX 022)
- Canada USA UL Certificate of Compliance Hazardous Location UL E106378 cULus (CoC E106378 RepRef E106378-20100930)
HiCTB16-TRX-RAS-PL-AI16: frequently asked questions
When can HiCTB16-TRX-RAS-PL-AI16 be shipped?
HiCTB16-TRX-RAS-PL-AI16 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up HiCTB16-TRX-RAS-PL-AI16 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for HiCTB16-TRX-RAS-PL-AI16 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for HiCTB16-TRX-RAS-PL-AI16, subject to availability and destination.
More Pepperl Fuchs parts