IFM PNI024
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can PNI024 be shipped?
PNI024 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up PNI024 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for PNI024 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for PNI024, subject to availability and destination.
Evaluation of external voltage or current values Continuous comparison of set/actual values directly in the sensor Automatic adjustment of the switch point Clearly visible 4-digit LED display Efficient differential pressure monitoring
Specifications
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range[bar] [bar] | 0...10 |
| Process connection | threaded connection G 1/4 internal thread |
Application
| Special feature | Gold-plated contacts |
| Application | for industrial applications |
| Media | liquids and gases |
| Medium temperature[°C] [°C] | -25...80 |
| Min. burst pressure | 150 bar; 15 MPa |
| 150 bar | 15 MPa |
| Pressure rating | 50 bar; 5 MPa |
| 50 bar | 5 MPa |
| Type of pressure | relative pressure |
Electrical data
| Operating voltage[V] [V] | 18...30 DC |
| Current consumption[mA] [mA] | < 90 |
| Min. insulation resistance[MΩ] [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time[s] [s] | 0.2 |
| Integrated watchdog | yes |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2 |
Inputs
| Analogue input (current)[mA] [mA] | 0...20 |
| Input resistance[Ω] [Ω] | 300 |
| Analogue input (voltage)[V] [V] | 0...10 |
| Input resistance[kΩ] [kΩ] | 90 |
Outputs
| Total number of outputs | 2 |
| Output signal | switching signal |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC[V] [V] | 2 |
| Permanent current rating of switching output DC[mA] [mA] | 250 |
| Switching frequency DC[Hz] [Hz] | < 170 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Measuring range[bar] [bar] | 0...10 |
| Set point SP[bar] [bar] | -2.46...10 |
| Note on setpoint SP | differential pressure |
| Reset point rP[bar] [bar] | -2.5...9.96 |
| Note on reset point rP | differential pressure |
| In steps of[bar] [bar] | 0.02 |
Accuracy / deviations
| Characteristics deviation[% of the final value] [% of the final value] | < ± 0,6 |
| Temperature drift per 10 K | < ± 0.3 |
| Characteristics deviation analogue input | < ± 0.3 |
| Temperature drift analogue input per 10 K | < ± 0.1 |
| Temperature drift analogue input[°C] [°C] | 0...80 |
Response times
| Response time[ms] [ms] | < 3 |
| Delay time programmable dS, dr[s] [s] | 0, 0,1...50 |
| Damping process value dAP[s] [s] | 0...4 |
Software / programming
| Adjustment of the switch point | programming button |
| Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; current/voltage input; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit |
Operating conditions
| Ambient temperature[°C] [°C] | -25...80 |
| Storage temperature[°C] [°C] | -40...100 |
| Protection | IP 65 |
Tests / approvals
| EMC | EN 61000-4-2 ESD; 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated; 10 V/m; EN 61000-4-4 Burst; 2 kV; EN 61000-4-6 HF conducted; 10 V |
| EN 61000-4-2 ESD | 4 kV CD / 8 kV AD |
| EN 61000-4-3 HF radiated | 10 V/m |
| EN 61000-4-4 Burst | 2 kV |
| EN 61000-4-6 HF conducted | 10 V |
| Shock resistance | DIN IEC 68-2-27; 50 g (11 ms) |
| DIN IEC 68-2-27 | 50 g (11 ms) |
| Vibration resistance | DIN IEC 68-2-6; 20 g (10...2000 Hz) |
| DIN IEC 68-2-6 | 20 g (10...2000 Hz) |
| MTTF[years] [years] | 152 |
| Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data
| Weight[g] [g] | 289 |
| Housing | cylindrical |
| Dimensions[mm] [mm] | Ø 34 / L = 91.5 |
| Materials | stainless steel (303/1.4305); PBT; PC; PA; FKM |
| Materials (wetted parts) | stainless steel (303/1.4305); ceramics; FKM |
| Min. pressure cycles | 100 million |
| Process connection | threaded connection G 1/4 internal thread |
| Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements
| Display | Display unit; 3 x LED, green; display mode; 3 x LED, green; switching status; 2 x LED, yellow; function display; alphanumeric display, 4-digit; measured values; alphanumeric display, 4-digit |
| Display unit | bar; psi; MPa |
| display mode | 3 x LED, green |
| switching status | 2 x LED, yellow |
| function display | alphanumeric display, 4-digit |
| measured values | alphanumeric display, 4-digit |
Remarks
| Pack quantity | 1 pcs. |
Electrical connection
| Connector | 1 x M12; coding: A; Contacts: gold-plated |