IFM AC6001
Quick facts
| Availability | Confirmed on request |
| Category | IO-Link - Masters for field applications in the food industry |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can AC6001 be shipped?
AC6001 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up AC6001 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for AC6001 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for AC6001, subject to availability and destination.
Simple replacement of units due to integrated parameter memory High protection rating for the requirements of the food and beverage industry For connection of up to four IO-Link devices Reliable transmission of machine data, process parameters and diagnostic data to the controller
Specifications
Application
| Application | hygienic and wet areas in the food industry |
| Daisy-chain function | power supply; fieldbus interface |
Electrical data
| Operating voltage[V] [V] | 18...31.6 DC; (AS-i) |
| Current consumption[mA] [mA] | 300...1500; (AUX) |
| Max. current consumption from AS-i[mA] [mA] | 100 |
| Protection class | III |
| Max. current load total[A] [A] | 1.1; (ports 1+2: 0,55 (AUX); ports 3+4: 0,55 (AUX)) |
| Additional voltage supply[V] [V] | 20...30 DC; (AUX) |
Inputs / outputs
| Total number of inputs and outputs | 8; (configurable) |
| Number of inputs and outputs | Number of digital inputs: 8; Number of digital outputs: 4 |
Inputs
| Number of digital inputs | 8; (IO-Link Port Class A: 4 x 2) |
| Sensor supply of the inputs | AUX |
| Switching level high[V] [V] | 11...30 |
| Switching level low[V] [V] | 0...5 |
| Digital inputs protected against short circuits | yes |
Outputs
| Number of digital outputs | 4; (IO-Link Port Class A: 4 x 1) |
| Max. current load per output[mA] [mA] | 300 |
| Short-circuit proof | yes |
| Actuator supply outputs | AUX |
Interfaces
| Communication interface | IO-Link; AS-i |
| Transmission type | COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
| IO-Link revision | 1.1 |
| Number of ports class A | 4 |
Operating conditions
| Ambient temperature[°C] [°C] | -25...60 |
| Storage temperature[°C] [°C] | -25...85 |
| Max. relative air humidity[%] [%] | 90 |
| Protection | IP 65; IP 66; IP 67; IP 69K; (operation with stainless steel protective caps: IP 69K) |
| Protection rating (NEMA 250) | 6P |
| Pollution degree | 2 |
| Chemical media | ISO 16750-5; HLP, CC, DB, DC, DD, CA; NEMA 250 5.13.1; AA |
| ISO 16750-5 | HLP, CC, DB, DC, DD, CA |
| NEMA 250 5.13.1 | AA |
Tests / approvals
| EMC | EN 61000-6-2; EN 61000-6-4 |
| Shock resistance | DIN EN 60068-2-27 |
| Vibration resistance | DIN EN 60068-2-64 2009-04; DIN EN 60068-2-6 2008-10 |
| MTTF[years] [years] | 161 |
AS-i classification
| AS-i version | 2.11; 3.0 |
| Extended addressing mode | no |
| AS-i profile | basic slave (CTT1 input); S-7.4.E; additional slave (CTT1 input); S-7.3.E; additional slave (CTT1 output); S-7.3.2 |
| basic slave (CTT1 input) | S-7.4.E |
| additional slave (CTT1 input) | S-7.3.E |
| additional slave (CTT1 output) | S-7.3.2 |
| Number of AS-i devices | 1...5 |
Mechanical data
| Weight[g] [g] | 255 |
| Housing | rectangular |
| Type of mounting | backplane mounting |
| Dimensions[mm] [mm] | 124 x 59.3 x 38.4 |
| Materials | housing: PA grey; socket: stainless steel (316L/1.4404) |
Electrical connection
| Module connection | M12 |
Remarks
| Remarks | For further information please see the operating instructions. |
| Pack quantity | 1 pcs. |
Electrical connection - IO-Link
| Connector | 4 x M12; coding: A |
Electrical connection - power supply IN
| Connector | 1 x M12; coding: A |
Electrical connection - power supply OUT
| Connector | 1 x M12; coding: A |