B&R X20AI4636
I/O module, 4 analog inputs ±10 V or 0 to 20 mA
- MPN
- X20AI4636
- Category
- Analog inputs
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
What is the B&R X20AI4636?
4 analog inputs
Current or voltage signal configuration for the entire module
16-bit digital converter resolution
Minimum conversion time of 40 µs for all inputs
The conversion time for the entire module can be configured in 0.02 µs steps.
Maximum 14 samples (16-bit) for the entire module per X2X Link cycle
Oversampling: Up to 16 analog values per channel (internal)
Timestamp for the last conversion of an X2X Link cycle
The module is equipped with 4 inputs with 16-bit digital converter resolution. It is possible to select between the current and voltage signal using different terminals. With the oversampling function, up to 16 analog values per channel can be recorded.
Specifications
Short description
| I/O module | 4 analog inputs ±10 V or 0 to 20 mA |
General information
| Diagnostics – Module run/error | Yes, using LED status indicator and software |
| Diagnostics – Inputs | Yes, using LED status indicator and software |
| Diagnostics – Channel type | Yes, using software |
| Power consumption – Bus | 0.01 W |
| Power consumption – Internal I/O | 1.5 W (note: To reduce power dissipation, B&R recommends bridging unused inputs on the terminal.) |
| Certifications – CE | Yes |
| Certifications – UKCA | Yes |
| Certifications – CRA (Cyber Resilience Act) | In preparation |
| Certifications – ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X |
| Certifications – UL | cULus E115267; Industrial control equipment |
| Certifications – HazLoc | cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5 |
| Certifications – DNV | Temperature: B (0 to 55°C); Humidity: B (up to 100%); Vibration: B (4 g); EMC: B (bridge and open deck) |
| Certifications – CCS | Yes |
| Certifications – LR | ENV1 |
| Certifications – KR | Yes |
| Certifications – ABS | Yes |
| Certifications – BV | EC33B ; Temperature: 5 - 55°C; Vibration: 4 g; EMC: Bridge and open deck |
| Certifications – KC | Yes |
| B&R ID code | 0xB3A8 |
| Status indicators | I/O function per channel, operating state, module status |
| Additional power dissipation caused by actuators (resistive) [W] | - |
Analog inputs
| Digital converter resolution – Voltage | ±15-bit |
| Digital converter resolution – Current | 15-bit |
| Output format – Voltage | INT 0x8001 - 0x7FFF / 1 LSB = 0x0001 = 305.176 µV |
| Output format – Current | INT 0x0000 - 0x7FFF / 1 LSB = 0x0001 = 610.352 nA |
| Input impedance in signal range – Voltage | 20 MΩ |
| Input impedance in signal range – Current | - |
| Load – Voltage | - |
| Load – Current | <400 Ω |
| Permissible input signal – Voltage | Max. ±30 V |
| Permissible input signal – Current | Max. ±50 mA |
| Output of digital value during overload – Voltage | 0x8001 |
| Output of digital value during overload – Current | 0x0000 |
| Output of digital value during overload – Voltage | 0x7FFF |
| Output of digital value during overload – Current | 0x7FFF |
| Max. error – Gain | 0.08% (note: Based on the current measured value.) |
| Max. error – Offset | 0.01% (note: Based on the 20 V measurement range.) |
| Max. error – Gain | 0.08% (note: Based on the current measured value.) |
| Max. error – Offset | 0.02% (note: Based on the 20 mA measurement range.) |
| Max. gain drift – Voltage | 0.01%/°C (note: Based on the current measured value.) |
| Max. gain drift – Current | 0.01%/°C (note: Based on the current measured value.) |
| Max. offset drift – Voltage | 0.001%/°C (note: Based on the 20 V measurement range.) |
| Max. offset drift – Current | 0.002%/°C (note: Based on the 20 mA measurement range.) |
| Common-mode rejection – DC | 70 dB |
| Common-mode rejection – 50 Hz | 70 dB |
| Nonlinearity – Voltage | <0.01% (note: Based on the 20 V measurement range.) |
| Nonlinearity – Current | <0.015% (note: Based on the 20 mA measurement range.) |
| Input | ±10 V or 0 to 20 mA, via different terminal connections |
| Input type | Differential input |
| Conversion time | 40 μs for all inputs |
| Output format | INT |
| Input protection | Protection against wiring with supply voltage |
| Conversion procedure | SAR |
| Input filter | Hardware - Third-order low-pass filter / cutoff frequency 10 kHz |
| Common-mode range | ±12 V |
| Crosstalk between channels | <-70 dB |
| Insulation voltage between channel and bus | 500 V eff |
Electrical properties
| Electrical isolation | Channel isolated from bus; Channel not isolated from channel |
Operating conditions
| Mounting orientation – Horizontal | Yes |
| Mounting orientation – Vertical | Yes |
| Installation elevation above sea level – 0 to 2000 m | No limitation |
| Installation elevation above sea level – >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature – Horizontal mounting orientation | -25 to 60°C |
| Temperature – Vertical mounting orientation | -25 to 50°C |
| Temperature – Derating | See section "Derating". |
| Temperature – Storage | -40 to 85°C |
| Temperature – Transport | -40 to 85°C |
| Relative humidity – Operation | 5 to 95%, non-condensing |
| Relative humidity – Storage | 5 to 95%, non-condensing |
| Relative humidity – Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order 1x terminal block X20TB12 separately.; Order 1x bus module X20BM11 separately. |
| Pitch | 12.5 +0.2 mm |
Accessories
Required accessories (order separately)
| X20BM15 | Bus modules — The bus module is the base for all X20 24 VDC I/O modules; The internal I/O supply is interconnected; Manual node number assignment; Indepe… |
| X20BM11 | Bus modules — Bus module for 24 VDC I/O modules; The internal I/O power supply is connected through. The bus module is the base for all 24 VDC I/O module… |
| X20TB12 | Terminal blocks — Tool-free wiring with push-in technology; Simple wire release using lever; Ability to label each terminal; Plain text labeling also possibl… |
Downloads & documentation
Official documents from B&R, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (15)
- 2226379 CSA Certificate of Compliance X20 X67
- 64331_A1 BV Certificate of Compliance X20
- ABS Certificate of Product Design Assessment - X20 IO Series
- CCS Type Approval Certificate - X20
- E115267 UL Certificate of Compliance X20
- EU Data Act - X20 IO - Connected Product Information Notice
- EU Declaration ATEX X20
- EU Declaration of conformity PLC X20
- FTZU 09 ATEX 0083X
- KR Type Approval Certificate MIL39390-AC003 (X20 System)
- Lloyds Register (X20 only)
- RINA Type Approval Certificate - X20 / Power Panel T30
- TAA00000BJ DNV Type Approval Certificate X20
- UK Declaration PLC X20
- X20, X67 KC certificates
X20AI4636: frequently asked questions
When can X20AI4636 be shipped?
X20AI4636 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up X20AI4636 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for X20AI4636 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20AI4636, subject to availability and destination.
More B&R parts