Pepperl Fuchs NMB2-12GM80-US-FE
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Inductive Sensors |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can NMB2-12GM80-US-FE be shipped?
NMB2-12GM80-US-FE is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up NMB2-12GM80-US-FE in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for NMB2-12GM80-US-FE and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for NMB2-12GM80-US-FE, subject to availability and destination.
Inductive sensor. Metal face proximity sensors, metal face, Switching function: Normally open (NO), Output type: Two-wire, Installation: flush, Output polarity: AC/DC, Output type: 2-wire, Thread mold: M12, Construction type: Cylindrical, thread, Series: Cylindrical type, Type of voltage: UC, Rated operating voltage: 20 ... 250 V AC/DC, Connection type: cable, Housing material: Stainless steel 1.4305 / AISI 303, Degree of protection: IP67, Material: PUR. Switching function: Normally open (NO). Output type: Two-wire. Rated operating distance: 2 mm. Installation: flush. Output polarity: AC/DC. Assured operating distance: 0 ... 1.62 mm. Actuating element: Ferrous targets. Reduction factor rAl: 0. Reduction factor rCu: 0. Reduction factor r304: 0.4 - 0.7. Reduction factor rSt37: 1. Reduction factor rBrass: 0. Output type: 2-wire. Switching frequency: 30 Hz. Hysteresis: 3 ... 15 typ. 5 %. Reverse polarity protection: yes. Short-circuit protection: yes. Voltage drop: ≤ 7 V. Rated operating current: 8 ... 200 mA AC/DC. Off-state current: ≤ 1.3 mA. Error indicator: LED, green/yellow (Alternate Flashing) - Short circuit/overload indication. Operation indicator: Dual LEDGreen: powerYellow: output. Rated operating voltage: 20 ... 250 V AC/DC. Standard conformity: . StandardsEN IEC 60947-5-2: . Standards: EN IEC 60947-5-2. UL approval: cULus Listed Load Type: Resistive Enclosure Type Rating: Type 1. CCC approval: Certified by China Compulsory Certification (CCC). Ambient temperature: -25 ... 70 °C (-13 ... 158 °F). Connection type: cable. Housing material: Stainless steel 1.4305 / AISI 303. Sensing face: Stainless steel 1.4305 / AISI 303. Degree of protection: IP67. Cable: . MaterialPURColorblackNumber of cores3Core cross section0.34 mm2LengthL2 m: . Material: PUR. Color: black. Number of cores: 3. Core cross section: 0.34 mm2. Length: 2 m. Dimensions: . Length80 mmDiameter12 mm: . Length: 80 mm. Diameter: 12 mm
Specifications
General specifications
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 2 mm sn |
| Installation | flush |
| Output polarity | AC/DC |
| Assured operating distance | 0 ... 1.62 mm sa |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.4 - 0.7 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Output type | 2-wire |
Nominal ratings
| Switching frequency | 30 Hz f |
| Hysteresis | 3 ... 15 typ. 5 % H |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | ≤ 7 V Ud |
| Rated operating current | 8 ... 200 mA AC/DC Ie |
| Off-state current | ≤ 1.3 mA Ir |
| Error indicator | LED, green/yellow (Alternate Flashing) - Short circuit/overload indication |
Indicators/operating means
| Operation indicator | Dual LEDGreen: powerYellow: output |
Electrical specifications
| Rated operating voltage | 20 ... 250 V AC/DC Ue |
Compliance with standards and directives
| Standard conformity | |
| StandardsEN IEC 60947-5-2 | Standards |
| Standards | EN IEC 60947-5-2 |
Approvals and certificates
| UL approval | cULus Listed Load Type: Resistive Enclosure Type Rating: Type 1 |
| CCC approval | Certified by China Compulsory Certification (CCC) |
Ambient conditions
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications
| Connection type | cable |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Degree of protection | IP67 |
| Cable | |
| MaterialPURColorblackNumber of cores3Core cross section0.34 mm2LengthL2 m | Material |
| Material | PUR |
| Color | black |
| Number of cores | 3 |
| Core cross section | 0.34 mm2 |
| Length | 2 m L |
| Dimensions | |
| Length80 mmDiameter12 mm | Length |
| Length | 80 mm |
| Diameter | 12 mm |