B&R 8I74S200037.00-000
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Weight | 1.65 kg |
Shipping & availability
When can 8I74S200037.00-000 be shipped?
8I74S200037.00-000 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 8I74S200037.00-000 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 8I74S200037.00-000 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 8I74S200037.00-000, subject to availability and destination.
ACOPOSinverter P74new, 1x 200-240 V, 0.37 kW, integrated EMC filter and brake chopper, shield plate included in delivery.
Specifications
Specifications
| CE | Yes |
| UL | UL E225616Power conversion equipment |
| CSA | CSA E272421Industrial control equipment |
| Specified on nameplate | 0.37 kW (0.5 HP) |
| Mains input voltage | 1x 200 VAC -15% to 240 VAC +10% |
| Frequency | 50 to 60 Hz ±5% |
| Apparent power (at 240 VAC) | 1.2 kVA |
| Max. assumed short-circuit current (Isc)(short-circuit current at connection point) | 1 kA |
| Inrush current | Max. 9.6 A |
| At 200 VAC | 6 A |
| At 240 VAC | 5 A |
| Power dissipation at nominal load and nominal clock frequency | 38 W |
| Integrated EMC filter | Yes |
| Motor cable length per IEC/EN 61800-3 Cat. C1 environment 1 (public power network) | C1 level of 2 to 16 kHz with 20 m cable |
| Motor cable length per IEC/EN 61800-3 Cat. C2 environment 1 (public power network) | C2 level of 2 to 6 kHz with 50 m cableC2 level at 2 kHz with 100 m cable |
| Motor cable length per IEC/EN 61800-3 Cat. C3 environment 2 (industrial power system) | 50 m |
| With add-on filter | 8I0FS009.200-2 |
| Nominal output current | 3.3 A |
| At nominal clock frequency (4 kHz) | No derating (up to 50°C) |
| Other clock frequencies | The derating curves are included in the installation instructions, which can be downloaded from www.br-automation.com. |
| Starting at 1000 m above sea level | 1%, per 100 m |
| Max. transient current for 60 s | 5 A |
| Max. transient current for 2 s | 5.5 A |
| Output frequency range | 0.1 to 599 Hz |
| Nominal clock frequency | 4 kHz |
| Min. | 2 kHz |
| Max. | 16 kHz |
| With braking resistor | Up to 170% of the nominal motor torque |
| Shielded cable | 50 m |
| Non-shielded cable | 100 m |
| Induction motor | Sensorless vector control:1. With V/f characteristic curve for constant torque→ Default profile2. With V/f characteristic curve for quadratically increasing torque→ Energy-saving profile, e.g. for fans and pumpsSensorless slip control:1. With V/f characteristic curve for constant torque→ Default profile2. With V/f characteristic curve for constant torque (6 f ranges)→ Profile for individual special applications3. With V/f characteristic curve for quadratically increasing torque→ Energy-saving profile, e.g. for fans and pumps |
| Synchronous motor | Sensorless vector control:1. With V/f characteristic curve for constant torque→ Default profile |
| Main protective functions of inverter | Thermal protection against power stage overheatingProtection against short circuits between motor phases, overcurrent between output phases and ground, overvoltages on the DC bus, exceeding the speed limit. Safety function for: Overvoltage and undervoltage of the mains supply, mains phase failure with 3-phase power supply |
| Integrated dynamic brake transistors | Yes |
| Min. resistance value (external) | 40 Ω |
| Input voltage | 24 VDC (-15%/+20%) |
| Current | 800 Ω |
| Output voltage 24 VDC | 24 VDC (-15%/+20%) |
| Max. output current at 24 VDC | 100 mA |
| Output voltage 10 VDC | 10 VDC (-0%/+10%) |
| Max. output current at 10 VDC | 10 mA |
| Type | Type 2 |
| Quantity | 1 |
| Nominal voltage | 30 VDC / 250 VAC |
| Input circuit | Sink |
| Current consumption | 16 mA |
| Input - ACOPOSinverter | Yes |
| Input - Input | No |
| Sampling time | 2 ms |
| Input impedance | 1.5 kΩ |
| Max. input frequency | 20 kHz |
| Low | <2 V |
| High | >17 V |
| Voltage | 470 Ω |
| Resolution | 10-bit |
| Max. voltage | 30 VDC |
| Output circuit | Source or sink |
| Max. current | 100 mA |
| Switching capacity | R1, with resistive load (cos phi = 1): 3 A at 250 VAC, R1, with resistive load (cos phi = 1): 4 A at 30 VDC, R1, R2, with inductive load (cos = 0.4 and L/R = 7 ms): 2 A at 250 VAC, R1, R2, with inductive load (cos = 0.4 and L/R = 7 ms): 2 A at 30 VDC, R2 with resistive load (cos phi = 1): 5 A at 250 VAC, R2 with resistive load (cos phi = 1): 5 A at 30 VDC |
| Relay 1 | 1 changeover contact |
| Relay 2 | 1 normally open contact |
| Output - ACOPOSinverter | Yes |
| Output - Output | No |
| Response time (max.) | 2 ms |
| Output | 0 to 10 V or 0 to 20 mA |
| Update time | 2 ms |
| Degree of protection per EN 60529 | IP20 |
| Relative humidity per IEC 60068-2-3 | 5 to 95%. non-condensingNo dripping water |
| Maximum installation elevation | Up to 2000 m |
| Max. pollution degree per IEC/EN 61800-5-1 | 2 (non-conductive pollution) |
| Ambient conditions per IEC 60721-3-3 | Class 3C3 and 3S3 |
| Operating position | Vertical mounting orientation ±10% |
| Operation | -10 to 50°C without derating50 to 60°C with derating |
| Storage | -25 to 70°C |
| Max. vibration resistance | 1 gn 13 to 200 Hz EN/IEC 60068-2-61.5 mm peak to peak 3 to 13 Hz EN/IEC 60068-2-6 |
| Width | 45 mm |
| Height | 317 mm |
| Depth | 245 mm |
| Weight | 1.646 kg |