2-channel analog input; Thermocouple K; Diagnostics, adjustable
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | I/O Systems |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can 753-469/003-000 be shipped?
753-469/003-000 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 753-469/003-000 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 753-469/003-000 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 753-469/003-000, subject to availability and destination.
<p>This analog input module directly connects to two thermocouples. Internal electrical isolation allows operation of grounded sensors.</p><p>The module automatically linearizes the entire temperature range.</p><p>Cold junction compensation mitigates the clamping unit offset voltage over the 0–55°C operating range.</p><p>A line break is indicated by a red LED. A green LED indicates readiness for operation and error-free communication with the coupler.</p><p>The shield directly connects to the DIN-rail.</p>
Specifications
Notes
| Note | Pluggable connectors and coding fingers (753 Series) are not included. |
Technical data
| Number of analog inputs | 2 |
| Total number of channels (module) | 2 |
| Signal type | Thermocouple, Low voltages |
| Signal type (configurable) | yes |
| Sensor connection | 2 x (2-wire) |
| Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) |
| Internal resistance | 1000 kΩ |
| Resolution (over entire range) | 0.1 °C |
| Conversion time (typ.) | 320 ms |
| Measurement error (25 °C) | < ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K) |
| Temperature coefficient | < ±0.2 K/K |
| Sensor types | Thermocouple K; Configurable: L, J, E, T, N, U, B, R, S, mV |
| Temperature range | Sensor-specific |
| Cold junction compensation | at each pair of terminal blocks |
| Supply voltage (system) | 5 VDC; via data contacts |
| Current consumption (5 V system supply) | 65 mA |
| Isolation | 500 V system/field |
| Indicators | LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2 |
Connection data
| Connection technology: I/O | 8 x CAGE CLAMP® |
| Connectable conductor materials | Copper |
| Connection type | Inputs/Outputs |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
Physical data
| Width | 12 mm / 0.472 inches |
| Height | 100 mm / 3.937 inches |
| Depth | 69.8 mm / 2.748 inches |
| Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
Mechanical data
| Mounting type | DIN-35 rail |
| Pluggable connector | Pluggable |
Material data
| Housing material | Polycarbonate; polyamide 6.6 |
| Fire load | 0.653 MJ |
| Weight | 43.5 g |
| Conformity marking | CE |
Environmental requirements
| Ambient temperature (operation) | 0 … +55 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Protection type | IP20 |
| Pollution degree | 2 per IEC 61131-2 |
| Operating altitude | 0 … 2000 m / 0 … 6562 ft |
| Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom |
| Relative humidity (without condensation) | 95 % |
| Vibration resistance | 4g per IEC 60068-2-6 |
| Shock resistance | 15g per IEC 60068-2-27 |
| EMC immunity to interference | per EN 61000-6-2, marine applications |
| EMC emission of interference | per EN 61000-6-4, marine applications |
| Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
| Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 % | 10 ppm |
| Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 % | 25 ppm |
Commercial data
| Product Group | 15 (I/O System) |
| PU (SPU) | 1 pcs |
| Packaging type | box |
| Country of origin | DE |
| GTIN | 4045454394509 |
| Customs tariff number | 85389099990 |
Product Classification
| UNSPSC | 32101602 |
| eCl@ss 10.0 | 27-24-26-01 |
| eCl@ss 9.0 | 27-24-26-01 |
| ETIM 9.0 | EC001596 |
| ETIM 10.0 | EC001596 |
| ECCN | NO US CLASSIFICATION |
Environmental Product Compliance
| CAS-No. | 1303-86-2, 1317-36-8, 25550-51-0, 7439-92-1 |
| REACH Candidate List Substance | 4-Methyl-1,2-cyclohexanedicarboxylic anhydride, Diboron trioxide, Lead, Lead monoxide |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I, 7(c)-II |
| SCIP notification number (Austria) | b1e3bf70-2792-406c-80d2-9665d9d3fa95 |
| SCIP notification number (Belgium) | 04799048-3485-42b5-a890-a35831085106 |
| SCIP notification number (Bulgaria) | b98e1e5e-a5a1-46c2-abfc-cd538e179489 |
| SCIP notification number (Czech Republic) | 0125135f-692a-4bda-b0e4-fb5dc47325b8 |
| SCIP notification number (Denmark) | b3c518cd-7a2a-4639-a06f-7d2afcc72e9e |
| SCIP notification number (Finland) | 2986d0b0-d843-40f8-b496-f2502c662b19 |
| SCIP notification number (France) | 20744723-0368-4744-9bbe-5df09ae64e02 |
| SCIP notification number (Germany) | bfc48183-6547-4e59-9d87-691e00813bb8 |
| SCIP notification number (Hungary) | 13190424-84b8-4f92-99b5-b7f942f6478e |
| SCIP notification number (Italy) | b1033583-229c-49ab-b1a0-bbfae755e09c |
| SCIP notification number (Netherlands) | e7a35b9b-f474-479a-8141-ba7113fdca5c |
| SCIP notification number (Poland) | 21fe5c18-1310-4f23-9136-2a6da31000e1 |
| SCIP notification number (Romania) | 18d6edff-1c5d-4703-a81f-bd06fe2c0614 |
| SCIP notification number (Sweden) | f5d0003f-40dd-4a57-bbfc-ae8907f560fb |