Schneider Electric OTB1C0DM9LP – I/O distributed module OTB - CANopen bus - 0..1000 m
Discontinued by Schneider Electric — we can still source the original OTB1C0DM9LP (new, used or refurbished, subject to availability). Request a quote below.
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Twido |
| Lifecycle | Discontinued |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Country of origin | FR |
| UPC / EAN | 3595863824339 |
| Recommended replacement | TM3BCCO |
| Datasheet | Manufacturer datasheet ↗ |
Shipping & availability
Can I still buy the OTB1C0DM9LP now that it is discontinued?
Yes. Schneider Electric has discontinued the OTB1C0DM9LP, but sourcing discontinued parts is what PartnerPLC specialises in — new old stock, used and refurbished units. Request a quote and we'll confirm availability, condition and lead time. If you are planning an upgrade instead, Schneider Electric names the TM3BCCO as its successor — we can quote both.
When can OTB1C0DM9LP be shipped?
OTB1C0DM9LP is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up OTB1C0DM9LP in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for OTB1C0DM9LP and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for OTB1C0DM9LP, subject to availability and destination.
Schneider Electric OTB1C0DM9LP — I/O distributed module OTB - CANopen bus - 0..1000 m (Advantys OTB). Discontinued by Schneider Electric; the manufacturer's successor is TM3BCCO. PartnerPLC sources discontinued and surplus Schneider Electric automation parts — request a quote for price, condition and lead time.
Specifications
Main
| Range of product | Modicon OTB |
| Product or component type | I/O distributed module |
| Integrated connection type | CANopen bus SUB-D 9, transmission mode: 2 twisted shielded pairs at 10 kbit/s...1 Mbit/s |
| Bus type | CANopen S20, profile: DS 401 V2.1, method of access: CSMA/MA multimaster with priority conforming to DR303-2; CANopen S20, profile: DS 401 V2.1, method of access: CSMA/MA multimaster with priority conforming to DS301 V4.02 |
| Discrete input number | 12 conforming to EN/IEC 61131 type 1 |
| Discrete input logic | Sink or source |
| Discrete input current | 5 mA for I0...I1; 5 mA for I6...I7; 7 mA for I2...I5; 7 mA for I8...I11 |
| Discrete output number | 2 solid state PNP for Q0...Q1 output logic: source; 6 relay for Q2...Q7 |
| Discrete output current | 2000 mA for relay; 300 mA for solid state |
Complementary
| Topology | Devices linked by daisy-chaining or tap junctions |
| Number of server device(s) | 63 |
| Bus length | 0…100 m tap-off length: 0…10 m, 500 kbit/s; 0…1000 m tap-off length: 0…120 m, 50 kbit/s; 0…250 m tap-off length: 0…10 m, 250 kbit/s; 0…2500 m tap-off length: 0…300 m, 20 kbit/s; 0…40 m tap-off length: 0…6 m, 800 kbit/s; 0…500 m tap-off length: 0…10 m, 125 kbit/s; 0…5000 m tap-off length: 0…600 m, 10 kbit/s; 0…20 m, 1 Mbit/s |
| Number of devices per segment | 0…16, length of segment <205 m; 0…32, length of segment <185 m; 0…64, length of segment <160 m |
| Discrete input voltage | 24 V |
| Discrete input voltage type | DC |
| Discrete input type | NPN or PNP |
| Input voltage limits | 20.4...26.4 V |
| Electronic filtering time | 0.035 ms for I0...I1 at state 1; 0.035 ms for I6...I7 at state 1; 0.04 ms for I2...I5 at state 1; 0.04 ms for I8...I11 at state 1; 0.045 ms for I0...I1 at state 0; 0.045 ms for I6...I7 at state 0; 0.15 ms for I2...I5 at state 0; 0.15 ms for I8...I11 at state 0 |
| Configurable filtering time | 12 ms; 0 ms; 3 ms |
| Input impedance | 3.4 kOhm for I2...I5; 3.4 kOhm for I8...I11; 5.7 kOhm for I0...I1; 5.7 kOhm for I6...I7 |
| Discrete output voltage | 24 V DC solid state output(s); 240 V AC relay output(s); 30 V DC relay output(s) |
| Output voltage limits | 20.4...28.8 V solid state |
| Maximum output current | 360 mA, solid state |
| Maximum current per output common | 8 A relay; 0.72 A solid state |
| Current consumption | 30 mA at 5 V DC (at state 1) relay output; 40 mA at 24 V DC (at state 1) relay output; 5 mA at 5 V DC (at state 0) relay output |
| Output overvoltage protection | 38...40 V |
| Maximum tungsten load | <8 W for solid state |
| Response time | 300 µs at state 0 for relay; 300 µs at state 1 for relay; 5 µs at state 0 for solid state; 5 µs at state 1 for solid state |
| Minimum switchable load | 0.1 mA |
| Contact bounce time | <= 1 ms for relay |
| Maximum leakage current | 0.1 mA at state 0 for solid state |
| Drop-out voltage | 1 V at state 1 |
| Insulation between channel and internal logic | 1500 Vrms for 1 minute for relay output; 500 Vrms for 1 minute for input circuit; 500 Vrms for 1 minute for solid state output |
| Insulation between channels | None |
| Contact resistance | 30 mOhm |
| Electrical durability | 500000 cycles AC-1 with 500 VA load for relay output; 500000 cycles AC-14 with 250 VA load for relay output; 500000 cycles AC-15 with 200 VA load for relay output; 500000 cycles DC-1 with 60 W load for relay output; 500000 cycles DC-13 with 30 W load for relay output |
| Supply circuit type | DC |
| [Us] rated supply voltage | 24 V |
| Supply voltage limits | 20.4…26.2 V |
| Input current | 700 mA at 26.2 V for supply circuit |
| Inrush current | 1 A for solid state output; 50 A for supply circuit |
| Power consumption in W | 19 W |
| Maximum number of I/O expansion module | 7 |
| I/O expansion capacity | 132 with screw terminal discrete I/O module(s); 188 with spring terminal discrete I/O module(s); 244 with HE10 connector discrete I/O module(s); 7 x 8I or 7 x 2I or 7 x (4I/2O) with screw terminal analogue I/O module(s) |
| Insulation resistance | >= 10 MOhm between I/O and earth terminals; >= 10 MOhm between power supply and earth |
| I/O connection | Removable screw terminal block |
| Number of common point | 1 for relay output (1 NO); 1 for relay output (2 NO); 1 for relay output (3 NO); 1 for input; 1 for solid state output |
| Counting input number | 2 |
| Counting capacity | 32 bits |
| Counting frequency | 20000 Hz; 5000 Hz |
| Pulse generator number | 2 |
| Pulse generator frequency | 7 kHz |
| Pulse generator function | RPWM pulse width modulation; RPLS pulse generator output |
| Marking | CE |
| Fixing mode | By clips (35 mm symmetrical DIN rail); By screws (panel with fixing kit); By screws (solid plate with fixing kit) |
| Status LED | 1 LED per channel (green) I/O; 1 LED (green) PWR; 1 LED (green) RUN; 1 LED (red) ERR |
| Net weight | 0.195 kg |
Environment
| IP degree of protection | IP20 |
| Immunity to microbreaks | 10 ms for supply circuit |
| Dielectric strength | 500 V between I/O and earth terminals; 500 V between power supply and earth |
| Standards | CSA; UL 508; EN 61131-2; CSA C22.2 No 213 Class I Division 2 Group D; CSA C22.2 No 213 Class I Division 2 Group B; CSA C22.2 No 213 Class I Division 2 Group A; IEC 61131-2; CSA C22.2 No 213 Class I Division 2 Group C |
| Product certifications | cULus |
| Ambient air temperature for operation | 0…55 °C |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 30…95 % without condensation |
| Pollution degree | 2 conforming to EN 60664; 2 conforming to IEC 60664 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 0.075 mm at 10…57 Hz on 35 mm symmetrical DIN rail; 1 gn at 57…150 Hz on 35 mm symmetrical DIN rail |
| Shock resistance | 15 gn for 11 ms conforming to EN 61131; 15 gn for 11 ms conforming to IEC 61131 |
| Resistance to electrostatic discharge | 4 kV in contact conforming to IEC 61000-4-2; 8 kV in air conforming to EN 61000-4-2; 8 kV in air conforming to IEC 61000-4-2; 4 kV in contact conforming to EN 61000-4-2 |
| Resistance to radiated fields | 10 V/m, radio frequency fields = 80000000…2000000000 Hz conforming to EN 61000-4-3; 10 V/m, radio frequency fields = 80000000…2000000000 Hz conforming to IEC 61000-4-3 |
| Resistance to fast transients | 1 kV (24 V solid state I/O) conforming to IEC 61000-4-4; 2 kV (24 V supply) conforming to IEC 61000-4-4 |
Downloads & documentation
Official documents from Schneider Electric, downloaded directly from the manufacturer.
Data sheets & manuals
| Product data sheet OTB1C0DM9LP |
More Schneider Electric parts
Available on requestPolyester glassreinf. plinth for encl. PLAZ(T)53 front opening IP44-IK10 RAL7035
Available on requestPolyester glassreinf. plinth for encl. PLAZ(T)54 front opening IP44-IK10 RAL7035
Available on requestPolyester glassreinf. plinth for encl. PLAZ(T)73 front opening IP44-IK10 RAL7035
Available on requestPolyester glassreinf. plinth for encl. PLAZ(T)74 front opening IP44-IK10 RAL7035
Available on requestI/O distributed module OTB - Ethernet TCP/IP - 0..100 m
Available on requestI/O distributed module OTB - Modbus non isolated serial link - 0..10 m
Available on requestpassive commoning module - for grouping inter-module I/O commons
Available on requestExiway Power Control Pico - central battery system - 6 Main cct 120 lum (Max)