Pepperl Fuchs RD0-TI-Ex8.FF.*
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Process Interfaces for FOUNDATION Fieldbus H1 |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can RD0-TI-Ex8.FF.* be shipped?
RD0-TI-Ex8.FF.* is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up RD0-TI-Ex8.FF.* in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for RD0-TI-Ex8.FF.* and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for RD0-TI-Ex8.FF.*, subject to availability and destination.
Temperature Multi-Input. Temperature multi-input, electronic component for control cabinet installation, For 8 temperature or analog sensors, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For FOUNDATION Fieldbus H1, IECEx approval, Dust protection, International, Europe, USA, Canada. Design / Mounting: Cabinet installation. Installation in hazardous area: Zone 1 / Div. 1. Fieldbus type: FOUNDATION Fieldbus. Physical layer profile: profile type 511 (FISCO), profile type 111 (Entity). ITK version: 6.2.0 (DEV_REV 02). Implementation: resource block 1x RSfunction block 8x AI, 1x MAItransducer block 8x sensor TB, 1x concentrator TB. Execution time: AI, MAI 40 ms max.. Macro cycle: typical for one device 8xAI or 1xMAI max. 500 ms. Firmware update: via separate plug connection. FDE (Fault Disconnect Equipment): 6.7 mA. Polarity: not polarity sensitive. Rated voltage: 9 ... 32 V. Rated current: max. 23 mA. LED PWR: green: on, bus voltage existent. LED COM ERR: red, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error. LED CHANNEL ERROR: red: 2 Hz flashing: lead breakage, overrange; off: no error. Number: 8. Sensor types: see table 1. Grounding: grounding of thermoelements possible. Error detection: lead breakage, wiring error, hardware device error. Common mode voltage: Input to Input 600 Vpeak. Deviation: . Cold junction compensation± 0.5 °C (32.9 °F)Resolution/accuracysee table 2Influence of ambient temperaturesee table 3LinearizationT/C input 0.1°C RTD input 0.03°C: . Cold junction compensation: ± 0.5 °C (32.9 °F). Resolution/accuracy: see table 2. Influence of ambient temperature: see table 3. Linearization: T/C input 0.1°C RTD input 0.03°C. Internal measurement cycle: for all sensor types max. 1 s. Fieldbus/inputs: safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V. Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013: . Directive 2014/30/EU: EN 61326-1:2013. Galvanic isolation: EN 60079-11. Electromagnetic compatibility: NE 21:2011. Degree of protection: IEC 60529. Fieldbus standard: IEC 61158-2. Shock resistance: EN 60068-2-27. Vibration resistance: EN 60068-2-6. Ambient temperature: -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area. Storage temperature: -40 ... 85 °C (-40 ... 185 °F). Relative humidity: ≤ 95 % non-condensing. Shock resistance: 15 g , 11 ms. Vibration resistance: 5 g , 10 ... 150 Hz. Corrosion resistance: acc. to ISA-S71.04-1985, severity level G3. Connection type: plug-in terminals , spring terminal and screw terminal. Core cross section: . Busup to 2.5 mm2Inputsup to 2.5 mm2: . Bus: up to 2.5 mm2. Inputs: up to 2.5 mm2. Housing material: Polycarbonate. Degree of protection: IP20. Mass: 360 g. Mounting: DIN rail mounting. EU-type examination certificate: PTB 03 ATEX 2237. Marking II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , [exsign] II (1) G [Ex ia Ga] IIC , [exsign] II (1) D [Ex ia Da] IIIC , [exsign] II 3 G Ex ic IIC T4 Gc: . Marking: II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , [exsign] II (1) G [Ex ia Ga] IIC , [exsign] II (1) D [Ex ia Da] IIIC , [exsign] II 3 G Ex ic IIC T4 Gc. Bus: FISCO see EC-Type Examination Certificate. Inputs: see EC-Type Examination Certificate. Certificate: PTB 03 ATEX 2238 X. Marking II 3 G Ex nA IIC T4 Gc: . Marking: II 3 G Ex nA IIC T4 Gc. Galvanic isolation: . Bussee Statement of ConformityInputsee EC-Type Examination Certificate: . Bus: see Statement of Conformity. Input: see EC-Type Examination Certificate. Directive conformity: . Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010: . Directive 2014/34/EU: EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010. FM approval: . FM certificateFM18US0054X , FM18CA0027XControl drawing16-473FM-12A: . FM certificate: FM18US0054X , FM18CA0027X. Control drawing: 16-473FM-12A. IECEx approval: . IECEx certificateIECEx PTB 05.0001 IECEx PTB 05.0002XIECEx markingEx ia [ia Ga] IIC T4 Gb [Ex ia Ga] IIC [Ex ia Da] IIIC Ex ic IIC T4 Gc Ex nA IIC T4 Gc: . IECEx certificate: IECEx PTB 05.0001 IECEx PTB 05.0002X. IECEx marking: Ex ia [ia Ga] IIC T4 Gb [Ex ia Ga] IIC [Ex ia Da] IIIC Ex ic IIC T4 Gc Ex nA IIC T4 Gc. Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Specifications
General specifications
| Design / Mounting | Cabinet installation |
| Installation in hazardous area | Zone 1 / Div. 1 |
Fieldbus connection
| Fieldbus type | FOUNDATION Fieldbus |
| Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) |
| ITK version | 6.2.0 (DEV_REV 02) |
| Implementation | resource block 1x RSfunction block 8x AI, 1x MAItransducer block 8x sensor TB, 1x concentrator TB |
| Execution time | AI, MAI 40 ms max. |
| Macro cycle | typical for one device 8xAI or 1xMAI max. 500 ms |
| Firmware update | via separate plug connection |
| FDE (Fault Disconnect Equipment) | 6.7 mA |
| Polarity | not polarity sensitive |
| Rated voltage | 9 ... 32 V UN |
| Rated current | max. 23 mA IN |
Indicators/operating means
| LED PWR | green: on, bus voltage existent |
| LED COM ERR | red, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error |
| LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange; off: no error |
Input
| Number | 8 |
| Sensor types | see table 1 |
| Grounding | grounding of thermoelements possible |
| Error detection | lead breakage, wiring error, hardware device error |
| Common mode voltage | Input to Input 600 Vpeak |
Transfer characteristics
| Deviation | |
| Cold junction compensation± 0.5 °C (32.9 °F)Resolution/accuracysee table 2Influence of ambient temperaturesee table 3LinearizationT/C input 0.1°C RTD input 0.03°C | Cold junction compensation |
| Cold junction compensation | ± 0.5 °C (32.9 °F) |
| Resolution/accuracy | see table 2 |
| Influence of ambient temperature | see table 3 |
| Linearization | T/C input 0.1°C RTD input 0.03°C |
| Internal measurement cycle | for all sensor types max. 1 s |
Galvanic isolation
| Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 61326-1:2013 | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 61326-1:2013 |
Standard conformity
| Galvanic isolation | EN 60079-11 |
| Electromagnetic compatibility | NE 21:2011 |
| Degree of protection | IEC 60529 |
| Fieldbus standard | IEC 61158-2 |
| Shock resistance | EN 60068-2-27 |
| Vibration resistance | EN 60068-2-6 |
Ambient conditions
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity | ≤ 95 % non-condensing |
| Shock resistance | 15 g , 11 ms |
| Vibration resistance | 5 g , 10 ... 150 Hz |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications
| Connection type | plug-in terminals , spring terminal and screw terminal |
| Core cross section | |
| Busup to 2.5 mm2Inputsup to 2.5 mm2 | Bus |
| Bus | up to 2.5 mm2 |
| Inputs | up to 2.5 mm2 |
| Housing material | Polycarbonate |
| Degree of protection | IP20 |
| Mass | 360 g |
| Mounting | DIN rail mounting |
Data for application in connection with hazardous areas
| EU-type examination certificate | PTB 03 ATEX 2237 |
| Marking II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , [exsign] II (1) G [Ex ia Ga] IIC , [exsign] II (1) D [Ex ia Da] IIIC , [exsign] II 3 G Ex ic IIC T4 Gc | Marking |
| Marking | II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , [exsign] II (1) G [Ex ia Ga] IIC , [exsign] II (1) D [Ex ia Da] IIIC , [exsign] II 3 G Ex ic IIC T4 Gc |
| Bus | FISCO see EC-Type Examination Certificate |
| Inputs | see EC-Type Examination Certificate |
| Certificate | PTB 03 ATEX 2238 X |
| Marking II 3 G Ex nA IIC T4 Gc | Marking |
| Marking | II 3 G Ex nA IIC T4 Gc |
| Galvanic isolation | |
| Bussee Statement of ConformityInputsee EC-Type Examination Certificate | Bus |
| Bus | see Statement of Conformity |
| Input | see EC-Type Examination Certificate |
| Directive conformity | |
| Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 | Directive 2014/34/EU |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
| FM approval | |
| FM certificateFM18US0054X , FM18CA0027XControl drawing16-473FM-12A | FM certificate |
| FM certificate | FM18US0054X , FM18CA0027X |
| Control drawing | 16-473FM-12A |
| IECEx approval | |
| IECEx certificateIECEx PTB 05.0001 IECEx PTB 05.0002XIECEx markingEx ia [ia Ga] IIC T4 Gb [Ex ia Ga] IIC [Ex ia Da] IIIC Ex ic IIC T4 Gc Ex nA IIC T4 Gc | IECEx certificate |
| IECEx certificate | IECEx PTB 05.0001 IECEx PTB 05.0002X |
| IECEx marking | Ex ia [ia Ga] IIC T4 Gb [Ex ia Ga] IIC [Ex ia Da] IIIC Ex ic IIC T4 Gc Ex nA IIC T4 Gc |
General information
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
More Pepperl Fuchs parts
NewPepperl + Fuchs KFD2-GUT-EX1.D New open box
Available on requestPepperl Fuchs V19-W-BK15M-PUR-U-V19-G
Available on requestPepperl Fuchs V1SD-G-GN65M-PUR-E1S-V45-G