Pepperl Fuchs KFD2-SR2-Ex2.2S
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | K-System (DIN Rail Mounting) |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can KFD2-SR2-Ex2.2S be shipped?
KFD2-SR2-Ex2.2S is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-SR2-Ex2.2S in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-SR2-Ex2.2S and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-SR2-Ex2.2S, subject to availability and destination.
Switch Amplifier. 2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection. Signal type: Digital Input. Safety Integrity Level (SIL): SIL 2. Connection: Power Rail or terminals 14+, 15-. Rated voltage: 20 ... 30 V DC. Ripple: ≤ 10 %. Rated current: ≤ 50 mA. Power dissipation: 1 W. Power consumption: < 1.3 W. Connection side: field side. Connection: terminals 1+, 2+, 3-; 4+, 5+, 6-. Rated values: acc. to EN 60947-5-6 (NAMUR). Open circuit voltage/short-circuit current: approx. 8 V DC / approx. 8 mA. Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA. Line fault detection: breakage I ≤ 0.1 mA , short-circuit I > 6 mA. Pulse/Pause ratio: min. 20 ms / min. 20 ms. Connection side: control side. Connection: output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12. Output I, II, III, IV: channel 1, 2; relay. Contact loading: 50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load. Minimum switch current: 1 mA / 24 V DC. Energized/De-energized delay: approx. 20 ms / approx. 20 ms. Mechanical life: 108 switching cycles. Collective error message: Power Rail. Switching frequency: ≤ 10 Hz. Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Output/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff. Output/Output: basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff. Display elements: LEDs. Control elements: DIP switch. Configuration: via DIP switches. Labeling: space for labeling at the front. Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013 (industrial locations): . Directive 2014/30/EU: EN 61326-1:2013 (industrial locations). Low voltage: . Directive 2014/35/EUEN 61010-1:2010: . Directive 2014/35/EU: EN 61010-1:2010. Electromagnetic compatibility: NE 21:2004. Degree of protection: IEC 60529:2001. Input: EN 60947-5-6:2000. Ambient temperature: -20 ... 60 °C (-4 ... 140 °F). Degree of protection: IP20. Connection: screw terminals. Mass: approx. 150 g. Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2. Height119 mmWidth20 mmDepth115 mm: . Height: 119 mm. Width: 20 mm. Depth: 115 mm. Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001. EU-type examination certificate: PTB 00 ATEX 2083. Marking II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]InputEEx ia IICVoltageUo10.5 VCurrentIo13 mAPowerPo34 mW (linear characteristic): . Marking: II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]. Input: EEx ia IIC. Voltage: 10.5 V. Current: 13 mA. Power: 34 mW (linear characteristic). Supply: . Maximum safe voltageUm253 V AC / 125 V DC (Attention! Um is no rated voltage.): Um. Maximum safe voltage: 253 V AC / 125 V DC (Attention! Um is no rated voltage.). Output: . Contact loading50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive loadMaximum safe voltageUm253 V AC (Attention! The rated voltage can be lower.): . Contact loading: 50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load. Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.). Certificate: TÜV 99 ATEX 1493 X. Marking II 3G Ex ec nC IIC T4 Gc: . Marking: II 3G Ex ec nC IIC T4 Gc. Galvanic isolation: . Input/inputnot availableInput/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VInput/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V: . Input/input: not available. Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V. Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V. Directive conformity: . Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019: . Directive 2014/34/EU: EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019. FM approval: . FM certificateFM19US0207XControl drawing116-0035: . FM certificate: FM19US0207X. Control drawing: 116-0035. CSA approval: . Control drawing116-0047: . Control drawing: 116-0047. IECEx approval: . IECEx certificateIECEx TUN 19.0013XIECEx markingEx ec nC IIC T4 Gc: . IECEx certificate: IECEx TUN 19.0013X. IECEx marking: Ex ec nC IIC T4 Gc. Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Specifications
General specifications
| Signal type | Digital Input |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 2 |
Supply
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 20 ... 30 V DC Ur |
| Ripple | ≤ 10 % |
| Rated current | ≤ 50 mA Ir |
| Power dissipation | 1 W |
| Power consumption | < 1.3 W |
Input
| Connection side | field side |
| Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output
| Connection side | control side |
| Connection | output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 |
| Output I, II, III, IV | channel 1, 2; relay |
| Contact loading | 50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load |
| Minimum switch current | 1 mA / 24 V DC |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Mechanical life | 108 switching cycles |
| Collective error message | Power Rail |
Transfer characteristics
| Switching frequency | ≤ 10 Hz |
Galvanic isolation
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff |
| Output/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff |
Indicators/settings
| Display elements | LEDs |
| Control elements | DIP switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 61326-1:2013 (industrial locations) | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Low voltage | |
| Directive 2014/35/EUEN 61010-1:2010 | Directive 2014/35/EU |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity
| Electromagnetic compatibility | NE 21:2004 |
| Degree of protection | IEC 60529:2001 |
| Input | EN 60947-5-6:2000 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 150 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height119 mmWidth20 mmDepth115 mm | Height |
| Height | 119 mm |
| Width | 20 mm |
| Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | PTB 00 ATEX 2083 |
| Marking II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]InputEEx ia IICVoltageUo10.5 VCurrentIo13 mAPowerPo34 mW (linear characteristic) | Marking |
| Marking | II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
| Input | EEx ia IIC |
| Voltage | 10.5 V Uo |
| Current | 13 mA Io |
| Power | 34 mW (linear characteristic) Po |
| Supply | |
| Maximum safe voltageUm253 V AC / 125 V DC (Attention! Um is no rated voltage.) | Um Maximum safe voltage |
| Maximum safe voltage | 253 V AC / 125 V DC (Attention! Um is no rated voltage.) Um |
| Output | |
| Contact loading50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive loadMaximum safe voltageUm253 V AC (Attention! The rated voltage can be lower.) | Contact loading |
| Contact loading | 50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) Um |
| Certificate | TÜV 99 ATEX 1493 X |
| Marking II 3G Ex ec nC IIC T4 Gc | Marking |
| Marking | II 3G Ex ec nC IIC T4 Gc |
| Galvanic isolation | |
| Input/inputnot availableInput/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VInput/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | Input/input |
| Input/input | not available |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity | |
| Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 | Directive 2014/34/EU |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 |
International approvals
| FM approval | |
| FM certificateFM19US0207XControl drawing116-0035 | FM certificate |
| FM certificate | FM19US0207X |
| Control drawing | 116-0035 |
| CSA approval | |
| Control drawing116-0047 | Control drawing |
| Control drawing | 116-0047 |
| IECEx approval | |
| IECEx certificateIECEx TUN 19.0013XIECEx markingEx ec nC IIC T4 Gc | IECEx certificate |
| IECEx certificate | IECEx TUN 19.0013X |
| IECEx marking | Ex ec nC IIC T4 Gc |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |