Pepperl Fuchs KFD2-PT2-Ex1-5
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | K-System (DIN Rail Mounting) |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can KFD2-PT2-Ex1-5 be shipped?
KFD2-PT2-Ex1-5 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-PT2-Ex1-5 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-PT2-Ex1-5 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-PT2-Ex1-5, subject to availability and destination.
Potentiometer Converter. 1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Current output 4 mA ... 20 mA, Lead resistance compensation adjustment, Accuracy 0.05 %, Housing width: 20 mm, Number of channels: 1-channel, Rated voltage: 20 ... 35 V DC, Type: 3-wire connection, Type [2]: 4-wire connection, Type [3]: 5-wire connection, Field device: potentiometer, Signal: 1 x 4 ... 20 mA. Signal type: Analog input. Connection: Power Rail or terminals 11+, 12-. Rated voltage: 20 ... 35 V DC. Ripple: within the supply tolerance. Power dissipation: 1 W. Power consumption: 1.3 W. Connection side: field side. Connection: terminals 4-, 5-, 3+, 2+, 1+. Potentiometer: . Types of measuring3-, 4-, 5-wire technologyNominal resistance800 Ω to 100 kΩSupply voltageapprox. 4.7 V: . Types of measuring: 3-, 4-, 5-wire technology. Nominal resistance: 800 Ω to 100 kΩ. Supply voltage: approx. 4.7 V. Lead resistance: 5 % of the potentiometer resistance (adjustable). Connection side: control side. Connection: terminals 7-, 8+. Current output: 4 ... 20 mA, load ≤1 kΩ. Accuracy: 0.05 %. Deviation: . Linearity± 10 µAInfluence of ambient temperature≤ 1 µA/K: . Linearity: ± 10 µA. Influence of ambient temperature: ≤ 1 µA/K. Rise time: 10 to 90 % ≤ 8 ms; 10 to 90 % within 1 % of span ≤ 25 ms. Output/power supply: functional insulation, rated insulation voltage 50 V AC. Control elements: potentiometer. Configuration: via potentiometer. Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013 (industrial locations): . Directive 2014/30/EU: EN 61326-1:2013 (industrial locations). Electromagnetic compatibility: NE 21:2012. Degree of protection: IEC 60529:2001. Protection against electrical shock: UL 61010-1. Ambient temperature: -20 ... 60 °C (-4 ... 140 °F). Degree of protection: IP20. Connection: screw terminals. Mass: approx. 120 g. Dimensions: 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1. Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001. EU-type examination certificate: BAS 00 ATEX 7171. Marking II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] IVoltageUo10.4 V DCCurrentIo31.4 mAPowerPo82 mW: . Marking: II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I. Voltage: 10.4 V DC. Current: 31.4 mA. Power: 82 mW. Supply: . Maximum safe voltageUm250 V (Attention! The rated voltage can be lower.): Um. Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.). Output: . Maximum safe voltageUm250 V (Attention! The rated voltage can be lower.): Um. Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.). Certificate: TÜV 02 ATEX 1797 X. Marking II 3G Ex nA II T4: . Marking: II 3G Ex nA II T4. Galvanic isolation: . Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VInput/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V: . Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V. Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V. Directive conformity: . Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010: . Directive 2014/34/EU: EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010. FM approval: . Control drawing116-0129: . Control drawing: 116-0129. UL approval: . Control drawing116-0173 (cULus): . Control drawing: 116-0173 (cULus). IECEx approval: . IECEx certificateIECEx BAS 10.0060 IECEx BAS 10.0061XIECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc: . IECEx certificate: IECEx BAS 10.0060 IECEx BAS 10.0061X. IECEx marking: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc. Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Specifications
General specifications
| Signal type | Analog input |
Supply
| Connection | Power Rail or terminals 11+, 12- |
| Rated voltage | 20 ... 35 V DC Ur |
| Ripple | within the supply tolerance |
| Power dissipation | 1 W |
| Power consumption | 1.3 W |
Input
| Connection side | field side |
| Connection | terminals 4-, 5-, 3+, 2+, 1+ |
| Potentiometer | |
| Types of measuring3-, 4-, 5-wire technologyNominal resistance800 Ω to 100 kΩSupply voltageapprox. 4.7 V | Types of measuring |
| Types of measuring | 3-, 4-, 5-wire technology |
| Nominal resistance | 800 Ω to 100 kΩ |
| Supply voltage | approx. 4.7 V |
| Lead resistance | 5 % of the potentiometer resistance (adjustable) |
Output
| Connection side | control side |
| Connection | terminals 7-, 8+ |
| Current output | 4 ... 20 mA, load ≤1 kΩ |
Transfer characteristics
| Accuracy | 0.05 % |
| Deviation | |
| Linearity± 10 µAInfluence of ambient temperature≤ 1 µA/K | Linearity |
| Linearity | ± 10 µA |
| Influence of ambient temperature | ≤ 1 µA/K |
| Rise time | 10 to 90 % ≤ 8 ms; 10 to 90 % within 1 % of span ≤ 25 ms |
Galvanic isolation
| Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings
| Control elements | potentiometer |
| Configuration | via potentiometer |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 61326-1:2013 (industrial locations) | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Electromagnetic compatibility | NE 21:2012 |
| Degree of protection | IEC 60529:2001 |
| Protection against electrical shock | UL 61010-1 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 120 g |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | BAS 00 ATEX 7171 |
| Marking II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] IVoltageUo10.4 V DCCurrentIo31.4 mAPowerPo82 mW | Marking |
| Marking | II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I |
| Voltage | 10.4 V DC Uo |
| Current | 31.4 mA Io |
| Power | 82 mW Po |
| Supply | |
| Maximum safe voltageUm250 V (Attention! The rated voltage can be lower.) | Um Maximum safe voltage |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) Um |
| Output | |
| Maximum safe voltageUm250 V (Attention! The rated voltage can be lower.) | Um Maximum safe voltage |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) Um |
| Certificate | TÜV 02 ATEX 1797 X |
| Marking II 3G Ex nA II T4 | Marking |
| Marking | II 3G Ex nA II T4 |
| Galvanic isolation | |
| Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VInput/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | Input/Output |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity | |
| Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 | Directive 2014/34/EU |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
| FM approval | |
| Control drawing116-0129 | Control drawing |
| Control drawing | 116-0129 |
| UL approval | |
| Control drawing116-0173 (cULus) | Control drawing |
| Control drawing | 116-0173 (cULus) |
| IECEx approval | |
| IECEx certificateIECEx BAS 10.0060 IECEx BAS 10.0061XIECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc | IECEx certificate |
| IECEx certificate | IECEx BAS 10.0060 IECEx BAS 10.0061X |
| IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
More Pepperl Fuchs parts
NewPepperl + Fuchs KFD2-GUT-EX1.D New open box
Available on requestPepperl Fuchs V19-W-BK15M-PUR-U-V19-G
Available on requestPepperl Fuchs V1SD-G-GN65M-PUR-E1S-V45-G