Pepperl Fuchs KFD2-GUT-1.D
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | K-System (DIN Rail Mounting, Highly Functional) |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can KFD2-GUT-1.D be shipped?
KFD2-GUT-1.D is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KFD2-GUT-1.D in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KFD2-GUT-1.D and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KFD2-GUT-1.D, subject to availability and destination.
Temperature Converter with Trip Values. 1-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Redundant TC input, Current output 0/4 mA ... 20 mA, 2 relay contact outputs, Configurable by PACTware or keypad, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Safety Integrity Level (SIL): SIL 2, Rated voltage: 20 ... 30 V DC, Field device: resistance thermometer. Signal type: Analog input. Safety Integrity Level (SIL): SIL 2. Connection: terminals 23+, 24- or power feed module/Power Rail. Rated voltage: 20 ... 30 V DC. Rated current: approx. 100 mA. Power dissipation/power consumption: ≤ 2 W / 2.2 W. Programming interface: programming socket. Connection side: field side. Connection: terminals 1, 2, 3, 4, 6. RTD: Pt100, Pt500, Pt1000, Ni100, Ni1000. Measuring currentapprox. 400 µATypes of measuring2-, 3-, 4-wire technologyLead resistancemax. 50 ΩMeasurement loop monitoringsensor breakage, sensor short-circuit: . Measuring current: approx. 400 µA. Types of measuring: 2-, 3-, 4-wire technology. Lead resistance: max. 50 Ω. Measurement loop monitoring: sensor breakage, sensor short-circuit. Thermocouples: type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995). Cold junction compensationexternal and internalMeasurement loop monitoringsensor breakage: . Cold junction compensation: external and internal. Measurement loop monitoring: sensor breakage. Potentiometer: 0.8 ... 20 kΩ. Types of measuring2-, 3-, 5-wire technology: . Types of measuring: 2-, 3-, 5-wire technology. Voltage: 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV. Open loop voltage: max. 5 V with resistance measuring sensor. Input resistance: ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV). Connection side: control side. Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7-. Output I, II: relay. Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 AMechanical life5 x 107 switching cyclesEnergized/De-energized delayapprox. 20 ms / approx. 20 ms: . Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A. Mechanical life: 5 x 107 switching cycles. Energized/De-energized delay: approx. 20 ms / approx. 20 ms. Output III: Analog current output. Current range0 ... 20 mA or 4 ... 20 mAOpen loop voltagemax. 24 V DCLoadmax. 650 ΩFault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43): . Current range: 0 ... 20 mA or 4 ... 20 mA. Open loop voltage: max. 24 V DC. Load: max. 650 Ω. Fault signal: downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43). Collective error message: Power Rail. Deviation: . Temperature effect Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of spanRTDmax. 0.2 % of spanThermocouplesmax. 10µV deviation of CJC: ±0.8 KVoltage0.1 % of spanPotentiometer0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩCurrent outputmax. 20 µA: . Temperature effect: Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span. RTD: max. 0.2 % of span. Thermocouples: max. 10µV deviation of CJC: ±0.8 K. Voltage: 0.1 % of span. Potentiometer: 0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩ. Current output: max. 20 µA. Sampling rate: approx. 700 ms. Input/Other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Output I, II against eachother: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Output III/power supply and collective error: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Interface/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Display elements: LEDs , display. Control elements: Control panel. Configuration: via operating buttons via PACTware. Labeling: space for labeling at the front. Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013 (industrial locations): . Directive 2014/30/EU: EN 61326-1:2013 (industrial locations). Low voltage: . Directive 2014/35/EUEN 61010-1:2010: . Directive 2014/35/EU: EN 61010-1:2010. Electromagnetic compatibility: NE 21:2007. Degree of protection: IEC 60529:2001. Ambient temperature: -20 ... 60 °C (-4 ... 140 °F). Degree of protection: IP20. Connection: screw terminals. Mass: 300 g. Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2. Height119 mmWidth40 mmDepth115 mm: . Height: 119 mm. Width: 40 mm. Depth: 115 mm. Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001. Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Specifications
General specifications
| Signal type | Analog input |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 2 |
Supply
| Connection | terminals 23+, 24- or power feed module/Power Rail |
| Rated voltage | 20 ... 30 V DC Ur |
| Rated current | approx. 100 mA Ir |
| Power dissipation/power consumption | ≤ 2 W / 2.2 W |
Interface
| Programming interface | programming socket |
Input
| Connection side | field side |
| Connection | terminals 1, 2, 3, 4, 6 |
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 |
| Measuring currentapprox. 400 µATypes of measuring2-, 3-, 4-wire technologyLead resistancemax. 50 ΩMeasurement loop monitoringsensor breakage, sensor short-circuit | Measuring current |
| Measuring current | approx. 400 µA |
| Types of measuring | 2-, 3-, 4-wire technology |
| Lead resistance | max. 50 Ω |
| Measurement loop monitoring | sensor breakage, sensor short-circuit |
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) |
| Cold junction compensationexternal and internalMeasurement loop monitoringsensor breakage | Cold junction compensation |
| Cold junction compensation | external and internal |
| Measurement loop monitoring | sensor breakage |
| Potentiometer | 0.8 ... 20 kΩ |
| Types of measuring2-, 3-, 5-wire technology | Types of measuring |
| Types of measuring | 2-, 3-, 5-wire technology |
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV |
| Open loop voltage | max. 5 V with resistance measuring sensor |
| Input resistance | ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV) |
Output
| Connection side | control side |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- |
| Output I, II | relay |
| Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 AMechanical life5 x 107 switching cyclesEnergized/De-energized delayapprox. 20 ms / approx. 20 ms | Contact loading |
| Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A |
| Mechanical life | 5 x 107 switching cycles |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Output III | Analog current output |
| Current range0 ... 20 mA or 4 ... 20 mAOpen loop voltagemax. 24 V DCLoadmax. 650 ΩFault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) | Current range |
| Current range | 0 ... 20 mA or 4 ... 20 mA |
| Open loop voltage | max. 24 V DC |
| Load | max. 650 Ω |
| Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) |
| Collective error message | Power Rail |
Transfer characteristics
| Deviation | |
| Temperature effect Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of spanRTDmax. 0.2 % of spanThermocouplesmax. 10µV deviation of CJC: ±0.8 KVoltage0.1 % of spanPotentiometer0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩCurrent outputmax. 20 µA | Temperature effect |
| Temperature effect | Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span |
| RTD | max. 0.2 % of span |
| Thermocouples | max. 10µV deviation of CJC: ±0.8 K |
| Voltage | 0.1 % of span |
| Potentiometer | 0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩ |
| Current output | max. 20 µA |
| Sampling rate | approx. 700 ms |
Galvanic isolation
| Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output III/power supply and collective error | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings
| Display elements | LEDs , display |
| Control elements | Control panel |
| Configuration | via operating buttons via PACTware |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 61326-1:2013 (industrial locations) | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Low voltage | |
| Directive 2014/35/EUEN 61010-1:2010 | Directive 2014/35/EU |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity
| Electromagnetic compatibility | NE 21:2007 |
| Degree of protection | IEC 60529:2001 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | 300 g |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Height119 mmWidth40 mmDepth115 mm | Height |
| Height | 119 mm |
| Width | 40 mm |
| Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |