Pepperl Fuchs KCD2-SCD-Ex1.SP
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | K-System (DIN Rail Mounting) |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can KCD2-SCD-Ex1.SP be shipped?
KCD2-SCD-Ex1.SP is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KCD2-SCD-Ex1.SP in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KCD2-SCD-Ex1.SP and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KCD2-SCD-Ex1.SP, subject to availability and destination.
SMART Current Driver. 1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART-IP and valve positioner, Lead breakage monitoring, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the field, HART communication, Safety Integrity Level (SIL): SIL 2, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC. Signal type: Analog output. Safety Integrity Level (SIL): SIL 2. Systematic capability (SC): SC 3. Connection: Power Rail or terminals 9+, 10-. Rated voltage: 19 ... 30 V DC. Ripple: ≤ 10 %. Rated current: ≤ 30 mA at 24 V. Power dissipation: ≤ 600 mW at 20 mA and 500 Ω load. Power consumption: ≤ 700 mW. Connection side: control side. Connection: terminals 5-, 6+. Input signal: 4 ... 20 mA , limited to approx. 26 mA. Input voltage: open loop voltage of the control system < 30 V. Voltage drop: approx. 6 V at 20 mA. Input resistance: > 100 kΩ, with field wiring open. Connection side: field side. Connection: terminals 1+, 2-. Voltage: ≥ 13 V at 20 mA. Current: 4 ... 20 mA. Load: 0 ... 650 Ω. Ripple: 20 mV rms. Deviation: at 20 °C (68 °F), 4 ... 20 mA< 0.1 % of full scale, incl. non-linearity and hysteresis. Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)): . Influence of ambient temperature: < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)). Frequency range: field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB). Rise time: 10 to 90 % ≤ 10 ms. Input/Output: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Input/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Output/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff. Display elements: LED. Labeling: space for labeling at the front. Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013 (industrial locations): . Directive 2014/30/EU: EN 61326-1:2013 (industrial locations). Electromagnetic compatibility: NE 21:2017 EN 61326-3-2:2018. Degree of protection: IEC 60529. Protection against electrical shock: UL 61010-1:2019. Ambient temperature: -40 ... 70 °C (-40 ... 158 °F). Degree of protection: IP20. Connection: spring terminals. Mass: approx. 100 g. Dimensions: 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2. Height124 mmWidth12.5 mmDepth114 mm: . Height: 124 mm. Width: 12.5 mm. Depth: 114 mm. Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001. EU-type examination certificate: CESI 06 ATEX 021 X. Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] IOutputEx ia: . Marking: II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I. Output: Ex ia. Supply: . Maximum safe voltageUm250 V AC (Attention! Um is no rated voltage.): Um. Maximum safe voltage: 250 V AC (Attention! Um is no rated voltage.). Equipment: terminals 1+, 2-. VoltageUo25.2 VCurrentIo100 mAPowerPo630 mWInternal capacitanceCi5.7 nFInternal inductanceLinegligible: Uo. Voltage: 25.2 V. Current: 100 mA. Power: 630 mW. Internal capacitance: 5.7 nF. Internal inductance: negligible. Certificate: CESI 19 ATEX 021 X. Marking II 3G Ex ec IIC T4 Gc: . Marking: II 3G Ex ec IIC T4 Gc. Galvanic isolation: . Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VOutput/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V: . Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V. Output/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V. Directive conformity: . Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018: . Directive 2014/34/EU: EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018. FM approval: . FM certificateFM 18 CA 0116 X , FM 19 US 0117 XControl drawing116-0469 (cFMus): . FM certificate: FM 18 CA 0116 X , FM 19 US 0117 X. Control drawing: 116-0469 (cFMus). UL approval: E106378. Control drawing116-0459 (cULus): . Control drawing: 116-0459 (cULus). IECEx approval: . IECEx certificateIECEx CES 06.0001XIECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc: . IECEx certificate: IECEx CES 06.0001X. IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc. Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Specifications
General specifications
| Signal type | Analog output |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 2 |
| Systematic capability (SC) | SC 3 |
Supply
| Connection | Power Rail or terminals 9+, 10- |
| Rated voltage | 19 ... 30 V DC Ur |
| Ripple | ≤ 10 % |
| Rated current | ≤ 30 mA at 24 V Ir |
| Power dissipation | ≤ 600 mW at 20 mA and 500 Ω load |
| Power consumption | ≤ 700 mW |
Input
| Connection side | control side |
| Connection | terminals 5-, 6+ |
| Input signal | 4 ... 20 mA , limited to approx. 26 mA |
| Input voltage | open loop voltage of the control system < 30 V |
| Voltage drop | approx. 6 V at 20 mA |
| Input resistance | > 100 kΩ, with field wiring open |
Output
| Connection side | field side |
| Connection | terminals 1+, 2- |
| Voltage | ≥ 13 V at 20 mA |
| Current | 4 ... 20 mA |
| Load | 0 ... 650 Ω |
| Ripple | 20 mV rms |
Transfer characteristics
| Deviation | at 20 °C (68 °F), 4 ... 20 mA< 0.1 % of full scale, incl. non-linearity and hysteresis |
| Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) | Influence of ambient temperature |
| Influence of ambient temperature | < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) |
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
| Rise time | 10 to 90 % ≤ 10 ms |
Galvanic isolation
| Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings
| Display elements | LED |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EUEN 61326-1:2013 (industrial locations) | Directive 2014/30/EU |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
| Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
| Degree of protection | IEC 60529 |
| Protection against electrical shock | UL 61010-1:2019 |
Ambient conditions
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | spring terminals |
| Mass | approx. 100 g |
| Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 |
| Height124 mmWidth12.5 mmDepth114 mm | Height |
| Height | 124 mm |
| Width | 12.5 mm |
| Depth | 114 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-type examination certificate | CESI 06 ATEX 021 X |
| Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] IOutputEx ia | Marking |
| Marking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Output | Ex ia |
| Supply | |
| Maximum safe voltageUm250 V AC (Attention! Um is no rated voltage.) | Um Maximum safe voltage |
| Maximum safe voltage | 250 V AC (Attention! Um is no rated voltage.) Um |
| Equipment | terminals 1+, 2- |
| VoltageUo25.2 VCurrentIo100 mAPowerPo630 mWInternal capacitanceCi5.7 nFInternal inductanceLinegligible | Uo Voltage |
| Voltage | 25.2 V Uo |
| Current | 100 mA Io |
| Power | 630 mW Po |
| Internal capacitance | 5.7 nF Ci |
| Internal inductance | negligible Li |
| Certificate | CESI 19 ATEX 021 X |
| Marking II 3G Ex ec IIC T4 Gc | Marking |
| Marking | II 3G Ex ec IIC T4 Gc |
| Galvanic isolation | |
| Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VOutput/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | Input/Output |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity | |
| Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018 | Directive 2014/34/EU |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018 |
International approvals
| FM approval | |
| FM certificateFM 18 CA 0116 X , FM 19 US 0117 XControl drawing116-0469 (cFMus) | FM certificate |
| FM certificate | FM 18 CA 0116 X , FM 19 US 0117 X |
| Control drawing | 116-0469 (cFMus) |
| UL approval | E106378 |
| Control drawing116-0459 (cULus) | Control drawing |
| Control drawing | 116-0459 (cULus) |
| IECEx approval | |
| IECEx certificateIECEx CES 06.0001XIECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | IECEx certificate |
| IECEx certificate | IECEx CES 06.0001X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
More Pepperl Fuchs parts
NewPepperl + Fuchs KFD2-GUT-EX1.D New open box
Available on requestPepperl Fuchs V19-W-BK15M-PUR-U-V19-G
Available on requestPepperl Fuchs V1SD-G-GN65M-PUR-E1S-V45-G

