Pepperl Fuchs F.SP5.P**.B**.1.0.***.***.***0
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Passive Splitters |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can F.SP5.P**.B**.1.0.***.***.***0 be shipped?
F.SP5.P**.B**.1.0.***.***.***0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up F.SP5.P**.B**.1.0.***.***.***0 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for F.SP5.P**.B**.1.0.***.***.***0 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for F.SP5.P**.B**.1.0.***.***.***0, subject to availability and destination.
Segment Protector Junction Box, Polyester (GRP). 4 ... 12 outputs Ex ic (FISCO or Entity), Glass fiber reinforced polyester, impact resistant, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: non-explosion hazardous area<BR>Zone 2 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk, Instrument location / spur protection: non-explosion hazardous area<BR>Zone 2 - all relevant types of protection<BR>Zone 1 - increased safety. Design / Mounting: Outside installation. Installed components: Segment Protector R2-SP-IC* For technical data on installed electronic component see data sheet.. Degree of protection: EN 60529. Ambient temperature: -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request). Storage temperature: -40 ... 70 °C (-40 ... 158 °F). Relative humidity: < 75 % (annual mean)< 95 % (30 d/year), no moisture condensation. Degree of protection: IP66. Dimensions: . W x H x D271 mm x 271 mm x 136 mm (1 x R2-SP-IC*) , 544 mm x 271 mm x 136 mm (2 x R2-SP-IC*): . W x H x D: 271 mm x 271 mm x 136 mm (1 x R2-SP-IC*) , 544 mm x 271 mm x 136 mm (2 x R2-SP-IC*). Mounting: thru-holes Ø6.5 mm. Certificate: PF 16 CERT 3134 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com. Marking II 3G Ex nA [ic] IIC T4 Gc [exsign] II 3D Ex tc [ic] IIIC T135°C Dc: . Marking: II 3G Ex nA [ic] IIC T4 Gc [exsign] II 3D Ex tc [ic] IIIC T135°C Dc. Directive conformity: . Directive 2014/34/EUEN 60079-0:2012 , EN 60079-15:2010 , EN 60079-31:2014: . Directive 2014/34/EU: EN 60079-0:2012 , EN 60079-15:2010 , EN 60079-31:2014. IECEx approval: IECEx PTB 09.0016 , suitable Junction Box on request
Specifications
General specifications
| Design / Mounting | Outside installation |
| Installed components | Segment Protector R2-SP-IC* For technical data on installed electronic component see data sheet. |
Conformity
| Degree of protection | EN 60529 |
Ambient conditions
| Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Relative humidity | < 75 % (annual mean)< 95 % (30 d/year), no moisture condensation |
Mechanical specifications
| Degree of protection | IP66 |
| Dimensions | |
| W x H x D271 mm x 271 mm x 136 mm (1 x R2-SP-IC*) , 544 mm x 271 mm x 136 mm (2 x R2-SP-IC*) | W x H x D |
| W x H x D | 271 mm x 271 mm x 136 mm (1 x R2-SP-IC*) , 544 mm x 271 mm x 136 mm (2 x R2-SP-IC*) |
| Mounting | thru-holes Ø6.5 mm |
Data for application in connection with hazardous areas
| Certificate | PF 16 CERT 3134 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com |
| Marking II 3G Ex nA [ic] IIC T4 Gc [exsign] II 3D Ex tc [ic] IIIC T135°C Dc | Marking |
| Marking | II 3G Ex nA [ic] IIC T4 Gc [exsign] II 3D Ex tc [ic] IIIC T135°C Dc |
| Directive conformity | |
| Directive 2014/34/EUEN 60079-0:2012 , EN 60079-15:2010 , EN 60079-31:2014 | Directive 2014/34/EU |
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-15:2010 , EN 60079-31:2014 |
International approvals
| IECEx approval | IECEx PTB 09.0016 , suitable Junction Box on request |