Available on request

B&R X20cCMR011 – I/O module, measurement of ambient conditions:

MPN: X20cCMR011 · Brand: B&R
Price on request
Request a Quote

A real person replies, typically within 1 business day — see our privacy policy.

12-month warranty (new) · 3-month (used/refurbished)
30-day returns, no restocking fee on unused parts
Ships via

Quick facts

AvailabilityConfirmed on request
CategoryOther functions
LifecycleActive
Warranty12-month (new) · 3-month (used/refurbished)

Shipping & availability

When can X20cCMR011 be shipped?

X20cCMR011 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up X20cCMR011 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for X20cCMR011 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for X20cCMR011, subject to availability and destination.

• Measurement and evaluation of the ambient conditions in the control cabinet

• Recording ambient conditions

• Recording operating hours and power-on cycles

• Saving user data directly on the module

• Supports blackout mode

• 2 inputs for PT1000 temperature sensors

• 2 digital inputs 24 VDC

• 1 digital output 24 VDC

Accessories

Required accessories (order separately)

X20cBM11Bus modules — Bus module for 24 VDC I/O modules; The internal I/O power supply is connected through.
X20TB12Terminal blocks — Tool-free wiring with push-in technology; Simple wire release using lever; Ability to label each terminal; Plain text labeling also possibl…

Specifications

Short description

I/O moduleMeasurement of ambient conditions:; Temperature in the module, relative humidity, vibration, shock, position, operating hours, power-on cycles; 2 digital inputs, 1 digital output, 2 Pt1000 temperature inputs

General information

Diagnostics – Module run/errorYes, using LED status indicator and software
Diagnostics – OutputYes, using LED status indicator and software (output error status)
Blackout mode – ScopeModule
Blackout mode – FunctionModule functionality
Blackout mode – Standalone modeNo
Power consumption – Bus0.4 W
Power consumption – Internal I/O0.1 W
Application memory – Type512 kB flash memory
Application memory – Sectors8 sectors, 64 kB each
Application memory – Data retention20 years at 55°C
Application memory – Guaranteed erase/write cycles100,000 per sector
Application memory – Error-correcting code (ECC)No
Application memory – Write protectionNo
Certifications – CEYes
Certifications – UKCAYes
Certifications – CRA (Cyber Resilience Act)In preparation
Certifications – DNVTemperature: B (0 to 55°C); Humidity: B (up to 100%); Vibration: B (4 g); EMC: B (bridge and open deck)
Certifications – LRENV1
Certifications – KRYes
Certifications – ABSYes
Certifications – BVEC33B ; Temperature: 5 - 55°C; Vibration: 4 g; EMC: Bridge and open deck
B&R ID code0x2A02
Status indicatorsI/O function per channel, overload, memory access, operating state, module status
Additional power dissipation caused by actuators (resistive) [W]+0.075

Digital inputs

Input filter – Hardware≤100 μs
Input filter – SoftwareDefault 1 ms, configurable between 0 and 25 ms in 0.2 ms increments
Switching threshold – Low<5 VDC
Switching threshold – High>15 VDC
Quantity2
Nominal voltage24 VDC
Input voltage24 VDC -15% / +20%
Input current at 24 VDCTyp. 3.75 mA
Input circuitSink
Connection type1-wire connections
Input resistanceTyp. 6.4 kΩ
Insulation voltage between channel and bus500 V eff

Resistance measurement temperature inputs

Sensor – Pt1000-40 to 125°C
Temperature sensor resolution – Pt10001 LSB = 0.1°C
Temperature measurement monitoring – Range undershoot0x8001
Temperature measurement monitoring – Range overshoot0x7FFF
Temperature measurement monitoring – Open circuit0x7FFF
Temperature measurement monitoring – General fault0x8000
Temperature measurement monitoring – Open inputs0x7FFF
Quantity2
InputResistance measurement for 2-wire connections
Digital converter resolution12-bit
Filter timeConfigurable
Conversion time1 ms for all inputs
Output formatINT
Input filterAveraging with clipping function
Linearization methodInternal
Permissible input signalShort-term ±15 V
Max. gain drift0.0003 %/°C
Max. offset drift0.06 %/°C
Nonlinearity<0.010%

Temperature and humidity sensor

Temperature measurement – Measurement range-25 to 125°C
Temperature measurement – Resolution0.1°C/LSB
Temperature measurement – Max. error±0.3°C
Humidity measurement – Measurement range5 to 95%
Humidity measurement – Resolution1%/LSB
Humidity measurement – Max. error±2% at 10 to 80% relative humidity; ±3% at <10 and >80% relative humidity
Sensor positionModule-internal
Sampling rate1 s

Acceleration and angle sensor

Acceleration measurement – Measurement range±16 g
Acceleration measurement – Resolution0.488 mg/LSB
Acceleration measurement – Linearity over temperature±1% at -40 to 85°C
Acceleration measurement – Offset calibration error±40 mg
Angular velocity measurement – Measurement range±2000 dps " data-placement="top" data-html="true" data-container="body" data-content="dps: Degrees per second (&#xB0;/s)">
Angular velocity measurement – Resolution±70 mdps per LSB
Angular velocity measurement – Linearity over temperature±1.5% at -40 to 85°C
Angular velocity measurement – Offset calibration error±10 dps
Sensor positionModule-internal
Sampling rateTyp. 10 ms

Digital outputs

Switching delay – 0 → 1<300 µs
Switching delay – 1 → 0<300 µs
Switching frequency – Resistive loadMax. 100 Hz
Switching frequency – Inductive loadSee section "Switching inductive loads".
Protective measures – Short-circuit proofYes
Protective measures – Overload-proofTemporary overload
Quantity1
VariantCurrent-sourcing FET
Nominal voltage24 VDC
Switching voltage24 VDC -15% / +20%
Nominal output current0.5 A
Connection type1- or 2-wire connections
Output circuitSource
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off120 µA
R DS(on)300 mΩ
Insulation voltage between channel and bus500 V eff

Electrical properties

Electrical isolationAnalog channel not isolated from bus; Digital channel isolated from bus; Digital channel not isolated from digital channel

Operating conditions

Mounting orientation – HorizontalYes
Mounting orientation – VerticalYes
Installation elevation above sea level – 0 to 2000 mNo limitation
Installation elevation above sea level – >2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20

Ambient conditions

Temperature – Horizontal mounting orientation-25 to 60°C
Temperature – Vertical mounting orientation-25 to 50°C
Temperature – Derating-
Temperature – Storage-40 to 85°C
Temperature – Transport-40 to 85°C
Relative humidity – OperationUp to 100%, condensing
Relative humidity – Storage5 to 95%, non-condensing
Relative humidity – Transport5 to 95%, non-condensing

Mechanical properties

NoteOrder 1x terminal block X20TB12 separately.; Order 1x bus module X20cBM11 separately.
Pitch12.5 +0.2 mm

Downloads & documentation

Official documents from B&R, downloaded directly from the manufacturer.

Data sheets & manuals

Data sheet X20(c)CMR011PDF · 4 MB · 1.05 (08/28/2025) - EN
X20 System User´s ManualPDF · 50 MB · 4.40 (03/10/2026) - EN

CAD & dimension drawings

3D File DXF/STEP X20 Electronic moduleZIP · 10 KB · 1.0 (10/17/2005)
3D File STEP X20 I/O-SliceZIP · 872 KB · 1.1 (03/13/2019)
Dimensions PDF X20 Electronic modulePDF · 3 KB · 1.0 (10/17/2005)
Certificates (8)
64331_A1 BV Certificate of Compliance X20PDF · 1 MB · 2026_05 (05/05/2026)
ABS Certificate of Product Design Assessment - X20 IO SeriesPDF · 454 KB · 2.00 (01/13/2025)
EU Data Act - X20 IO - Connected Product Information NoticePDF · 92 KB · 1.00 (09/30/2025)
EU Declaration ATEX X20PDF · 218 KB · 2023-07 (09/05/2023)
EU Declaration of conformity PLC X20PDF · 169 KB · 2021/10 (11/08/2021)
KR Type Approval Certificate MIL39390-AC003 (X20 System)PDF · 320 KB · 2.0 (05/05/2025)
Lloyds Register (X20 only)PDF · 884 KB · 1.30 (07/07/2025)
UK Declaration PLC X20PDF · 151 KB · 2024-01 (01/18/2024)
12-month warrantyon all new stock
3-month warrantyon used & refurbished parts
30-day returnsno restocking fee on unused parts
Global shippingFast, tracked delivery worldwide