Compact terminal block; for current transformer circuit; 6,00 mm²; multicoloured
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Rail-Mount Terminal Blocks |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can 2007-8875 be shipped?
2007-8875 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 2007-8875 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 2007-8875 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 2007-8875, subject to availability and destination.
<h2>Current transformer terminal block, 2007 Series, multi-colored</h2><br/><br/>Our current transformer terminal block (item number 2007-8875) is designed for seamless electrical installations. Conductors can only be connected to this current transformer terminal block if their strip length is between 13 and 15 mm . This product features conductor terminals and utilizes Push-in CAGE CLAMP®. Our Push-in CAGE CLAMP® is a universal, maintenance-free connection solution for all conductor types, boasting a key feature: It allows direct insertion of both solid and fine-stranded conductors with ferrules without needing tools. No preparation is required; for example, crimping the conductor's ferrule is not necessary. This current transformer terminal block is suitable for conductor cross sections ranging from 0.5 mm² to 10 mm².<br/><br/><h3></h3>
Specifications
Electrical data - Ratings per IEC/EN
| Nominal voltage (III/3) | 500 V |
| Rated impulse withstand voltage (III / 3) | 6 kV |
| Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
Electrical data - General information
| Wiring direction | Front-entry wiring |
Connection data
| Number of levels | 1 |
Connection data - Connection 1
| Connection technology | Push-in CAGE CLAMP® |
| Actuation type | Operating tool |
| Connectable conductor materials | Copper |
| Nominal cross-section | 6 mm² / 10 AWG |
| Solid conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Solid conductor; push-in termination | 1 … 10 mm² / 14 … 8 AWG |
| Fine-stranded conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Fine-stranded conductor; with insulated ferrule | 0.5 … 6 mm² / 20 … 10 AWG |
| Fine-stranded conductor; with uninsulated ferrule | 1.5 … 6 mm² / 16 … 10 AWG |
| Fine-stranded conductor; with ferrule; push-in termination | 2.5 … 6 mm² / 16 … 10 AWG |
| Strip length | 13 … 15 mm / 0.51 … 0.59 inches |
| Wiring direction | Front-entry wiring |
Physical data
| Width | 69.5 mm / 2.736 inches |
| Height | 99.6 mm / 3.921 inches |
| Depth from upper-edge of DIN-rail | 65.3 mm / 2.571 inches |
| Module width | 8 mm / 0.315 inches |
Mechanical data
| Mounting type | DIN-35 rail |
| Marking level | Center/side marking |
Material data
| Note (material data) | Information on material specifications can be found here |
| Color | multi-colored |
| Material group | I |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 3.243 MJ |
| Weight | 196.3 g |
| Test socket color | orange |
Environmental requirements
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
Environmental requirements - Environmental Testing
| Test specification: <br/>Railway applications –<br/>Rolling stock –<br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
| Test procedure: <br/>Railway applications – <br/>Rolling stock equipment – <br/>Vibration and shock tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
| Spectrum/Mounting location | Service life test, Category 1, Class A/B |
| Functional test with noise-like oscillations | Test passed according to Section 8 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.101g (highest test level used for all axes) |
| Test duration per axis | 10 min. |
| Test directions | X, Y and Z axes |
| Monitoring of contact faults and interruptions | Passed |
| Voltage drop measurement before and after each axis | Passed |
| Simulated service life test through increased levels of noise-like oscillations | Test passed according to Section 9 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.572g (highest test level used for all axes) |
| Test duration per axis | 5 h |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Shock test | Test passed according to Section 10 of the standard |
| Shock pulse form | Half sine |
| Acceleration | 5g (highest test level used for all axes) |
| Shock duration | 30 ms |
| Number of shocks (per axis) | 3 pos. und 3 neg. |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Vibration and shock stress for rolling stock equipment | Passed |
Commercial data
| PU (SPU) | 1 pcs |
| Packaging type | box |
| Country of origin | DE |
| GTIN | 4055143240628 |
| Customs tariff number | 85369010000 |
Product Classification
| UNSPSC | 39121410 |
| eCl@ss 10.0 | 27-14-11-47 |
| eCl@ss 9.0 | 27-14-11-47 |
| ETIM 9.0 | EC000276 |
| ETIM 10.0 | EC000276 |
| ECCN | NO US CLASSIFICATION |
Environmental Product Compliance
| CAS-No. | 7439-92-1 |
| REACH Candidate List Substance | Lead |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c) |
| SCIP notification number (Austria) | 07053267-9cc9-4e80-906b-02d5be984777 |
| SCIP notification number (Belgium) | 685df096-f420-40b6-9f02-22ca2e2f68c5 |
| SCIP notification number (Bulgaria) | 937ea640-7cef-460c-b21b-fe49b424eed0 |
| SCIP notification number (Czech Republic) | 51ac0922-116a-4d07-bbaf-b9e41c419a7f |
| SCIP notification number (Denmark) | 4868a345-19b9-4cff-8eb6-7c0e558555e5 |
| SCIP notification number (Finland) | abeb4353-af96-495f-90a7-c01747e86a10 |
| SCIP notification number (France) | d9d45c9a-5682-4945-8c60-2d2312480da6 |
| SCIP notification number (Germany) | a69750ee-6d53-4f74-a9b8-1c5cd9fd36fb |
| SCIP notification number (Hungary) | 2e0a58d0-c93f-4fb6-a60f-5e068332a48b |
| SCIP notification number (Italy) | 0c6a4315-bbcb-4f7e-b1e5-1ec21488e052 |
| SCIP notification number (Netherlands) | 925aee0d-4f2e-498a-a3b2-d58c3de04c17 |
| SCIP notification number (Poland) | c6f8d7e2-7ed2-4f73-a3e0-3c6f309da27f |
| SCIP notification number (Romania) | 19b7acdb-4cd4-4076-83fe-43da3ecdc81c |
| SCIP notification number (Sweden) | e5a18b15-4ef9-4f40-824e-ec7c83fee2e2 |