Compact terminal block; for current and voltage transformers; 6,00 mm²; multicoloured
Quick facts
| Availability | Confirmed on request |
| Category | Rail-Mount Terminal Blocks |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can 2007-8873 be shipped?
2007-8873 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 2007-8873 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 2007-8873 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 2007-8873, subject to availability and destination.
<h2>Current transformer terminal block, 2007 Series, multi-colored</h2><br/><br/>Our current transformer terminal block (item number 2007-8873) simplifies electrical installations. Ensure that the strip lengths are between 13 and 15 mm when connecting conductors to this current transformer terminal block. This product features conductor terminals and utilizes Push-in CAGE CLAMP®. Push-in CAGE CLAMP® connection technology is ideal for connecting all conductor types. It allows direct insertion of both solid and fine-stranded conductors with ferrules without needing to use any tools—all thanks to its pluggable design. Depending on the conductor type, this current transformer terminal block is suitable for conductor cross sections ranging from 0.5 mm² to 10 mm².<br/><br/><h3></h3>
Specifications
Electrical data - Ratings per IEC/EN
| Nominal voltage (III/3) | 500 V |
| Rated impulse withstand voltage (III / 3) | 6 kV |
| Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
Electrical data - General information
| Wiring direction | Front-entry wiring |
Connection data
| Number of levels | 1 |
Connection data - Connection 1
| Connection technology | Push-in CAGE CLAMP® |
| Actuation type | Operating tool |
| Connectable conductor materials | Copper, Copper |
| Nominal cross-section | 6 mm² / 10 AWG |
| Solid conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Solid conductor; push-in termination | 1 … 10 mm² / 14 … 8 AWG |
| Fine-stranded conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Fine-stranded conductor; with insulated ferrule | 0.5 … 6 mm² / 20 … 10 AWG |
| Fine-stranded conductor; with uninsulated ferrule | 1.5 … 6 mm² / 16 … 10 AWG |
| Fine-stranded conductor; with ferrule; push-in termination | 2.5 … 6 mm² / 16 … 10 AWG |
| Strip length | 13 … 15 mm / 0.51 … 0.59 inches |
| Wiring direction | Front-entry wiring |
Physical data
| Width | 112 mm / 4.409 inches |
| Height | 99.6 mm / 3.921 inches |
| Depth from upper-edge of DIN-rail | 65.3 mm / 2.571 inches |
| Module width | 8 mm / 0.315 inches |
Mechanical data
| Mounting type | DIN-35 rail, DIN-35 rail |
| Marking level | Center/side marking |
Material data
| Note (material data) | Information on material specifications can be found here |
| Color | multi-colored |
| Material group | I |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 5.578 MJ |
| Weight | 347.5 g |
| Test socket color | orange |
Environmental requirements
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
Environmental requirements - Environmental Testing
| Test specification: <br/>Railway applications –<br/>Rolling stock –<br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
| Test procedure: <br/>Railway applications – <br/>Rolling stock equipment – <br/>Vibration and shock tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
| Spectrum/Mounting location | Service life test, Category 1, Class A/B |
| Functional test with noise-like oscillations | Test passed according to Section 8 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.101g (highest test level used for all axes) |
| Test duration per axis | 10 min. |
| Test directions | X, Y and Z axes |
| Monitoring of contact faults and interruptions | Passed |
| Voltage drop measurement before and after each axis | Passed |
| Simulated service life test through increased levels of noise-like oscillations | Test passed according to Section 9 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.572g (highest test level used for all axes) |
| Test duration per axis | 5 h |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Shock test | Test passed according to Section 10 of the standard |
| Shock pulse form | Half sine |
| Acceleration | 5g (highest test level used for all axes) |
| Shock duration | 30 ms |
| Number of shocks (per axis) | 3 pos. und 3 neg. |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Vibration and shock stress for rolling stock equipment | Passed |
Commercial data
| Product Group | 22 (TOPJOB S) |
| PU (SPU) | 1 pcs |
| Packaging type | Box |
| Country of origin | DE |
| GTIN | 4050821776697 |
| Customs tariff number | 85369010000 |
Product Classification
| UNSPSC | 39121410 |
| eCl@ss 10.0 | 27-14-11-47 |
| eCl@ss 9.0 | 27-14-11-47 |
| ETIM 9.0 | EC000276 |
| ETIM 10.0 | EC000276 |
| ECCN | NO US CLASSIFICATION |
Environmental Product Compliance
| CAS-No. | 7439-92-1 |
| REACH Candidate List Substance | Lead |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c) |
| SCIP notification number (Austria) | 9a02a54f-67f0-4e40-8cc8-8aea0d730074 |
| SCIP notification number (Belgium) | d9d1a20b-28ce-40a3-b167-f49fdf4032c2 |
| SCIP notification number (Bulgaria) | 3d39520b-1fce-49bc-a0fc-dcb3a64777b9 |
| SCIP notification number (Czech Republic) | cfedf63f-df48-4e6f-aa7d-6e86c757639b |
| SCIP notification number (Denmark) | 84a46ab5-28c4-44b3-88b4-7eef1e1d695f |
| SCIP notification number (Finland) | 6586b91a-c192-4fd1-89a7-02d08adb8e98 |
| SCIP notification number (France) | b2926040-333e-4558-88fb-cd9c23ba5075 |
| SCIP notification number (Germany) | fe1cc17d-0dd0-40b1-8b47-feec55670a58 |
| SCIP notification number (Hungary) | f69d3ad2-f0a5-4771-8d4d-824ce92fd9ad |
| SCIP notification number (Italy) | eacfeb2b-3120-4519-a8f9-56c2e5f0f1b3 |
| SCIP notification number (Netherlands) | 2e859d8a-4d5a-4ce1-b3e0-3befd2b1e8c5 |
| SCIP notification number (Poland) | 6dfc79df-fceb-4607-a188-a8b3ccc82039 |
| SCIP notification number (Romania) | 496afc7e-0340-4fb2-8779-5948dd9da026 |
| SCIP notification number (Sweden) | fc2d2baa-f684-422a-badf-d87fd0ae14ad |