IFM SDG080
Quick facts
| Availability | Confirmed on request |
| Category | Systems for the consumption measurement of compressed air & industrial gases |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can SDG080 be shipped?
SDG080 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up SDG080 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for SDG080 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for SDG080, subject to availability and destination.
Precise measurement of flow and consumption High accuracy, repeatability and measurement dynamics For detecting compressed air in industrial use With switching output, analogue output and pulse output Clearly visible 4-digit LED display
Specifications
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
| Measuring range[m³/h] [m³/h] | 9...2750 |
| Process connection | flange DN80 according to:DIN EN 10220 |
Application
| Application | totaliser function |
| Media | compressed air |
| Note on media | air quality ISO 8573-1; class 141; class 344 |
| Medium temperature[°C] [°C] | 0...60 |
| Pressure rating | 16 bar; 1.6 MPa |
| 16 bar | 1.6 MPa |
Electrical data
| Operating voltage[V] [V] | 19...30 DC |
| Current consumption[mA] [mA] | < 100 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time[s] [s] | 0.5 |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs
| Total number of outputs | 2 |
| Output signal | switching signal; analogue signal; pulse signal; (configurable) |
| Electrical design | PNP |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC[V] [V] | 2 |
| Permanent current rating of switching output DC[mA] [mA] | 250; (per output) |
| Number of analogue outputs | 1 |
| Analogue current output[mA] [mA] | 4...20; (scalable) |
| Max. load[Ω] [Ω] | 500 |
| Pulse output | consumed quantity meter |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Measuring range[m³/h] [m³/h] | 9...2750 |
| Display range[m³/h] [m³/h] | 0...3300 |
| Pulse value | 1 Nm³ |
| Pulse length[s] [s] | 0,1 |
Accuracy / deviations
| Accuracy (in the measuring range) | ± (3 % MW + 0,3 % MEW) / ± (6 % MW + 0,6 % MEW); (class 141 /; class 344) |
Response times
| Response time[s] [s] | 0.1; (dAP = 0) |
Operating conditions
| Ambient temperature[°C] [°C] | 0...60 |
| Storage temperature[°C] [°C] | -20...85 |
| Max. relative air humidity[%] [%] | 90 |
| Protection | IP 65 |
Tests / approvals
| EMC | EN 61000-4-2 ESD; 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated; 10 V/m; EN 61000-4-4 Burst; 2 kV; EN 61000-4-6 HF conducted; 10 V |
| EN 61000-4-2 ESD | 4 kV CD / 8 kV AD |
| EN 61000-4-3 HF radiated | 10 V/m |
| EN 61000-4-4 Burst | 2 kV |
| EN 61000-4-6 HF conducted | 10 V |
| Vibration resistance | DIN IEC 68-2-6; 5 g (55...2000 Hz) |
| DIN IEC 68-2-6 | 5 g (55...2000 Hz) |
| MTTF[years] [years] | 214 |
Mechanical data
| Weight[g] [g] | 11625 |
| Housing | rectangular |
| Dimensions[mm] [mm] | 160 x 141 x 198 |
| Materials | PBT-GF20; PC; PC; stainless steel (304/1.4301); FKM; pipe section: steel galvanised |
| Materials (wetted parts) | stainless steel (316 / 1.4401); stainless steel (304/1.4301); ceramics glass passivated; PEEK; polyester; FKM; aluminium anodised; pipe section: steel galvanised |
| Process connection | flange DN80 according to:DIN EN 10220 |
Remarks
| Remarks | MW = measured value; MEW = Final value of the measuring range; Measuring, display and setting ranges refer to the standard volume flow according to DIN ISO 2533.; For information about installation and operation please see the operating instructions. |
| Pack quantity | 1 pcs. |
Electrical connection
| Connector | 1 x M12; coding: A |