Quick facts
| Availability | Confirmed on request |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can SA3010 be shipped?
SA3010 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up SA3010 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for SA3010 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for SA3010, subject to availability and destination.
Reliable monitoring of water in pipes Two switching outputs, one of them programmable as analogue output Easy setting of the switch points for quick set-up Robust housing for use in harsh industrial environments LED display for indication of the measured value
Specifications
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
| Measuring range[l/min] [l/min] | 0...10 |
| Process connection | threaded connection M26 x 1,5 internal thread |
Application
| Special feature | Gold-plated contacts |
| Installation | T-pieces; ((DIN 2353): QL 18-18-18 (NW 15 mm) / QL 22-18-22 (NW 19 mm) / QL 28-18-28 (NW 24 mm)) |
| Media | water |
| Medium temperature[°C] [°C] | 0...80 |
| Pressure rating | 30 bar; 3 MPa |
| 30 bar | 3 MPa |
Electrical data
| Operating voltage[V] [V] | 20...28 DC |
| Current consumption[mA] [mA] | < 80 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time[s] [s] | 10 |
| Measuring principle | calorimetric |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs
| Total number of outputs | 2 |
| Output signal | switching signal; analogue signal; (configurable) |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC[V] [V] | 2 |
| Permanent current rating of switching output DC[mA] [mA] | 250; (per output) |
| Number of analogue outputs | 1 |
| Analogue current output[mA] [mA] | 4...20; (scalable) |
| Max. load[Ω] [Ω] | 500 |
| Analogue voltage output[V] [V] | 0...10; (scalable) |
| Min. load resistance[Ω] [Ω] | 2000 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Measuring range[l/min] [l/min] | 0...10 |
| Display range[l/min] [l/min] | 0...12 |
| Set point SP[l/min] [l/min] | 0.1...12 |
| Reset point rP[l/min] [l/min] | 0...11.9 |
| Analogue start point ASP[l/min] [l/min] | 0...8 |
| Analogue end point AEP[l/min] [l/min] | 4...12 |
| In steps of[l/min] [l/min] | 0.1 |
Accuracy / deviations
| Repeatability[% of the measured value] [% of the measured value] | 3 (Q < 30%) / 7 (Q < 100%) |
| Temperature gradient[K/min] [K/min] | 200 |
| Accuracy (in the measuring range) | ± 10 |
Response times
| Response time[s] [s] | 5; (10%...90%) |
| Delay time programmable dS, dr[s] [s] | 0...50 |
Software / programming
| Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; current/voltage output; inside pipe diameter; start-up delay; adaptation of displayed values; display can be rotated and switched off; Display unit |
Operating conditions
| Ambient temperature[°C] [°C] | -20...60 |
| Protection | IP 67 |
Tests / approvals
| EMC | EN 61000-4-2 ESD; 4 kV CD / 8 kV AD; EN 61000-4-3 HF radiated; 10 V/m; EN 61000-4-4 Burst; 2 kV; EN 61000-4-6 HF conducted; 10 V |
| EN 61000-4-2 ESD | 4 kV CD / 8 kV AD |
| EN 61000-4-3 HF radiated | 10 V/m |
| EN 61000-4-4 Burst | 2 kV |
| EN 61000-4-6 HF conducted | 10 V |
| MTTF[years] [years] | 184 |
Mechanical data
| Weight[g] [g] | 330.5 |
| Housing | cylindrical |
| Dimensions[mm] [mm] | Ø 34 / L = 102 |
| Materials | stainless steel (316L/1.4404); PBT; PC; PA; EPDM/X; FKM |
| Materials (wetted parts) | stainless steel (316L/1.4404); O-ring: FKM 70 Shore A |
| Process connection | threaded connection M26 x 1,5 internal thread |
| Probe diameter[mm] [mm] | 14 |
Displays / operating elements
| Display | switching status; 2 x LED, red; measured values; 7-segment LED display; programming; 7-segment LED display |
| switching status | 2 x LED, red |
| measured values | 7-segment LED display |
| programming | 7-segment LED display |
| Display unit | l/min; gpm; l/h; gph; m³/h |
Remarks
| Remarks | NW = nominal diameter |
| Pack quantity | 1 pcs. |
Electrical connection
| Connector | 1 x M12; coding: A; Contacts: gold-plated |