Quick facts
| Availability | Confirmed on request |
| Category | Intuitive switch point setting |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can PK5524 be shipped?
PK5524 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up PK5524 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for PK5524 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for PK5524, subject to availability and destination.
Simple switch point setting via setting ring Stainless steel measuring cell, e.g. for freons in refrigerating technology Mechanical locking prevents inadvertent switch point manipulation High burst pressure For use in hydraulic and pneumatic applications
Specifications
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 1 |
| Measuring range | 0...10 bar; 0...145 psi |
| 0...10 bar | 0...145 psi |
| Process connection | threaded connection G 1/4 external thread internal thread:M5 |
Application
| Application | for industrial applications |
| Media | liquids and gases |
| Medium temperature[°C] [°C] | -25...80 |
| Min. burst pressure | 300 bar; 4350 psi; 30 MPa |
| 300 bar | 4350 psi |
| Pressure rating | 25 bar; 362 psi; 2.5 MPa |
| 25 bar | 362 psi |
| Type of pressure | relative pressure |
Electrical data
| Operating voltage[V] [V] | 9.6...32 DC |
| Current consumption[mA] [mA] | < 25 |
| Min. insulation resistance[MΩ] [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 1 |
Outputs
| Total number of outputs | 1 |
| Output signal | switching signal |
| Electrical design | PNP |
| Number of digital outputs | 1 |
| Output function | normally open |
| Max. voltage drop switching output DC[V] [V] | 2 |
| Permanent current rating of switching output DC[mA] [mA] | 500 |
| Switching frequency DC[Hz] [Hz] | 100 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Measuring range | 0...10 bar; 0...145 psi |
| 0...10 bar | 0...145 psi |
| Set point SP | 0.5...10 bar; 7.5...145 psi |
| 0.5...10 bar | 7.5...145 psi |
| Hysteresis | 0.2 bar; 2.9 psi |
| 0.2 bar | 2.9 psi |
Accuracy / deviations
| Switch point accuracy[% of the final value] [% of the final value] | < ± 2,5; (Setting accuracy) |
| Repeatability[% of the final value] [% of the final value] | < ± 0,5; (with temperature fluctuations < 10 K) |
| Characteristics deviation[% of the final value] [% of the final value] | < ± 1,5 (BFSL) / < ± 2,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Temperature drift per 10 K | < ± 0.5 |
Software / programming
| Adjustment of the switch point | setting ring |
Operating conditions
| Ambient temperature[°C] [°C] | -25...80 |
| Storage temperature[°C] [°C] | -40...100 |
| Protection | IP 67 |
Tests / approvals
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3 |
| Shock resistance | DIN IEC 68-2-27; 50 g (11 ms) |
| DIN IEC 68-2-27 | 50 g (11 ms) |
| Vibration resistance | DIN IEC 68-2-6; 20 g (10...2000 Hz) |
| DIN IEC 68-2-6 | 20 g (10...2000 Hz) |
| MTTF[years] [years] | 576 |
| Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Mechanical data
| Weight[g] [g] | 92.5 |
| Housing | cylindrical |
| Dimensions[mm] [mm] | Ø 27 / L = 71.6 |
| Materials | PBT; PC; FKM; stainless steel (316L/1.4404) |
| Materials (wetted parts) | stainless steel (316L/1.4404); FKM |
| Min. pressure cycles | 50 million |
| Tightening torque[Nm] [Nm] | 25 |
| Process connection | threaded connection G 1/4 external thread internal thread:M5 |
| Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements
| Display | operation; LED, green; switching status; LED, yellow |
| operation | LED, green |
| switching status | LED, yellow |
| With scale | yes |
Remarks
| Pack quantity | 1 pcs. |
Electrical connection
| Connector | 1 x M12; coding: A |