IFM LI2132
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Use in applications with coolants, cleaning agents and lubricants as well as hydraulic oils |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can LI2132 be shipped?
LI2132 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up LI2132 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for LI2132 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for LI2132, subject to availability and destination.
For the reliable point level monitoring in tanks and containers Detection of minimum level, leakage or overflow of tanks Easy empty and full adjustment by pressing just one pushbutton Suitable for water, oils and coolants With approval according to the German Federal Water Act (WHG) Integrated temperature measurement via IO-Link
Specifications
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2 |
| Factory setting | oils; oil-based media |
| Probe length L[mm] [mm] | 273 |
Application
| Special feature | Gold-plated contacts |
| Media | Liquids |
| Dielectric constant of the medium | > 1,8 |
| Recommended media | water; hydrous media; oils; oil-based media |
| Cannot be used for | See operating instructions, chapter "Intended use". |
| Medium temperature[°C] [°C] | -25...85; (applications subject to the German Federal Water Act 0...85°C) |
| Pressure rating | 0.5 bar; 0.05 MPa |
| 0.5 bar | 0.05 MPa |
| Vacuum resistance[mbar] [mbar] | -500 |
Electrical data
| Operating voltage[V] [V] | 9.6...35 DC; (IO-Link: 18...30 DC) |
| Current consumption[mA] [mA] | < 15 |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time[s] [s] | < 1 |
| Measuring principle | capacitive |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2 |
Outputs
| Total number of outputs | 2 |
| Output signal | switching signal; IO-Link |
| Electrical design | PNP/NPN |
| Number of digital outputs | 2 |
| Output function | OUT2; normally open / normally closed; (parameterisable) |
| OUT-OP | normally closed |
| OUT2 | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC[V] [V] | 2.5 |
| Permanent current rating of switching output DC[mA] [mA] | 100 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Factory setting | oils; oil-based media |
| Probe length L[mm] [mm] | 273 |
| Active range A[mm] [mm] | 28 |
| Measuring range[°C] [°C] | -25...85 |
Accuracy / deviations
| Accuracy[K] [K] | 1,5 |
| Resolution[K] [K] | 0.1 |
| Dynamic response T09[s] [s] | 240 |
Response times
| Response time[s] [s] | < 0.3 |
Interfaces
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.1 |
| SDCI standard | IEC 61131-9 |
| Profiles | Common - I&D; Identification and Diagnosis |
| Common - I&D | Identification and Diagnosis |
| SIO mode | yes |
| Required master port type | A |
| Process data analogue | 5 |
| Process data binary | 2 |
| Min. process cycle time[ms] [ms] | 4.5 |
| Supported DeviceIDs | default; 1588 |
| default | 1588 |
Operating conditions
| Ambient temperature[°C] [°C] | -25...85 |
| Storage temperature[°C] [°C] | -25...85 |
| Protection | IP 68; IP 69K; (7 days / 3 m water depth / 0.3 bar: IP 68) |
Tests / approvals
| Approval | WHG; General building authority approval; overflow prevention; leakage detection |
| EMC | DIN EN 61000-6-2; DIN EN 61000-6-3; in a closed metal tank; DIN EN 61000-6-4; in plastic or open metal tanks |
| DIN EN 61000-6-3 | in a closed metal tank |
| DIN EN 61000-6-4 | in plastic or open metal tanks |
| Shock resistance | DIN EN 60068-2-27; 12 g (11 ms) |
| DIN EN 60068-2-27 | 12 g (11 ms) |
| Vibration resistance | DIN EN 60068-2-6; 5 g (10...2000 Hz) |
| DIN EN 60068-2-6 | 5 g (10...2000 Hz) |
| MTTF[years] [years] | 433 |
| UL approval | UL approval no.; H013; File number UL; E174191 |
| UL approval no. | H013 |
| File number UL | E174191 |
Mechanical data
| Weight[g] [g] | 363.6 |
| Materials | PP reinforced fibre |
| Materials (wetted parts) | PP |
| Probe diameter[mm] [mm] | 16 |
Displays / operating elements
| Display | operation; LED, green; switching status; LED, yellow |
| operation | LED, green |
| switching status | LED, yellow |
| Operating elements | inductive programming button |
Remarks
| Pack quantity | 1 pcs. |
Electrical connection
| Connector | 1 x M12; coding: A; Contacts: gold-plated |