IFM KI0054
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | All capacitive sensors |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can KI0054 be shipped?
KI0054 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KI0054 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KI0054 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KI0054, subject to availability and destination.
Easy adjustment to the empty and full state via pushbutton For the detection of liquids and dry bulk materials With combined AC/DC output stage Two-wire technology Output function normally open / normally closed programmable
Specifications
Product characteristics
| Output function | normally open / normally closed; (selectable) |
| Sensing range[mm] [mm] | 5...40; (programming buttons) |
| Housing | threaded type |
| Dimensions[mm] [mm] | M30 x 1.5 / L = 90 |
Application
| Installation | detection through non-metallic container wall or on bypass pipes |
| Media | dry bulk material; liquids |
Electrical data
| Frequency AC[Hz] [Hz] | 47...63 |
| Operating voltage[V] [V] | 30...250 AC / 20...250 DC |
| Protection class | II |
| Reverse polarity protection | yes |
| Measuring principle | capacitive |
Outputs
| Output function | normally open / normally closed; (selectable) |
| Max. voltage drop switching output DC[V] [V] | 8 |
| Max. voltage drop switching output AC[V] [V] | 10 |
| Max. leakage current[mA] [mA] | 2.5 (250 V AC) / 1.7 (110 V AC) / 1.5 (24 V DC) |
| Permanent current rating of switching output AC[mA] [mA] | 100; (150 (...40 °C)) |
| Permanent current rating of switching output DC[mA] [mA] | 100; (150 (...40 °C)) |
| Short-time current rating of switching output[mA] [mA] | 1000; (20 ms / 0,5 Hz) |
| Switching frequency AC[Hz] [Hz] | 10 |
| Switching frequency DC[Hz] [Hz] | 10 |
| Short-circuit proof | no |
| Overload protection | no |
Detection zone
| Sensing range[mm] [mm] | 5...40; (programming buttons) |
| Sensing range adjustable | yes |
| Factory setting sensing range[mm] [mm] | 20 |
| Real sensing range Sr[mm] [mm] | 20 ± 10 % |
Accuracy / deviations
| Correction factor | glass: 0.3 / water: 1 / ceramics: 0.2 / PVC: 0.1 |
| Hysteresis[% of Sr] [% of Sr] | 1...15 |
| Switch point drift[% of Sr] [% of Sr] | -20...20 |
Operating conditions
| Ambient temperature[°C] [°C] | -25...80 |
| Note on ambient temperature | temperature of the sensing face: -25...110 °C |
| Protection | IP 65; IP 67 |
Tests / approvals
| EMC | EN 60947-5-2 |
| MTTF[years] [years] | 321 |
Mechanical data
| Weight[g] [g] | 89.1 |
| Housing | threaded type |
| Mounting | non-flush mountable |
| Dimensions[mm] [mm] | M30 x 1.5 / L = 90 |
| Thread designation | M30 x 1.5 |
| Materials | housing: PBT; pushbuttons: TPE-U; LED window: PC |
Displays / operating elements
| Display | switching status; 1 x LED ring, yellow plug lights translucently |
| switching status | 1 x LED ring, yellow plug lights translucently |
| Teach function | yes |
| Electronic lock | yes |
Electrical connection
| Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting |
Accessories
| Items supplied | lock nuts: 2 |
Remarks
| Remarks | Note:; Check the safe functioning of the unit after a short circuit. |
| Pack quantity | 1 pcs. |
Electrical connection - plug
| Connector | 1 x 1/2"; coding: C |