IFM DN4237
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | Field power supplies |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can DN4237 be shipped?
DN4237 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up DN4237 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for DN4237 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for DN4237, subject to availability and destination.
Protection of the wiring via configurable electronic circuit breakers Installation without control cabinet Additional diagnostics by measuring current, voltage and mains quality as well as counting operating hours Energy-efficient generation of extra-low voltage without power loss Output voltage, load currents, output circuit states and trigger cause are communicated via IO-Link Switching the output circuits on and off as well as resetting the circuit breakers is possible via IO-Link
Specifications
Electrical data
| Nominal voltage AC[V] [V] | 400 / 480 |
| Nominal frequency AC[Hz] [Hz] | 50...60 |
| Input voltage range AC[V] [V] | 323...552 |
| Output voltage DC[V] [V] | 24...28 |
| Protection class | I |
| Max. power-on delay time[ms] [ms] | 2000 |
| Output voltage tolerance[%] [%] | 0.2 |
| Max. output current at min. output voltage[A] [A] | 20.8 |
| Max. output current at max. output voltage[A] [A] | 17.8 |
| Output power (permanent)[W] [W] | 500 |
| Output power (peak)[W] [W] | 1000 |
| Power factor (nominal voltage 400 V AC / 50 Hz) | 0.94 |
| Power factor (nominal voltage 480 V AC / 50 Hz) | 0.95 |
| Number of output circuits | 4 |
| Switch-on peak current (nominal voltage 400 V AC / 60 Hz)[A] [A] | 2.1 |
| Switch-on peak current (nominal voltage 480 V AC / 50 Hz)[A] [A] | 2 |
| Efficiency (nominal voltage 400 V AC / 60 Hz)[%] [%] | 94.2 |
| Efficiency (nominal voltage 480 V AC / 50 Hz)[%] [%] | 94 |
| Mains buffering time (nominal voltage 400 V AC / 60 Hz)[ms] [ms] | 24 |
| Mains buffering time (nominal voltage 480 V AC / 50 Hz)[ms] [ms] | 24 |
| Input current (nominal voltage 400 V AC / 60 Hz)[A] [A] | 1.1 |
| Input current (nominal voltage 480 V AC / 50 Hz)[A] [A] | 0.9 |
Outputs
| Load capacitance, total[mF] [mF] | 12.5 |
Interfaces
| Communication interface | IO-Link |
| Transmission type | COM3 (230,4 kBaud) |
| IO-Link revision | 1.1 |
| Profiles | Common - I&D; Identification and Diagnosis |
| Common - I&D | Identification and Diagnosis |
| SIO mode | yes |
| Required master port type | A |
| Min. process cycle time[ms] [ms] | 2 |
| Supported DeviceIDs | default; 1270 |
| default | 1270 |
Operating conditions
| Ambient temperature[°C] [°C] | -25...70 |
| Storage temperature[°C] [°C] | -40...85 |
| Max. relative air humidity[%] [%] | 95; (relative humidity) |
| Max. height above sea level[m] [m] | 5000 |
| Protection | IP 65; IP 67 |
| Pollution degree | 3 |
Tests / approvals
| EMC | EN 61000-4-2 CD; 8 kV / failure criterion A; EN 61000-4-2 AD; 15 kV / failure criterion A; EN 61000-4-3; 80 Mhz...2.7 GHz / 20 V/m failure criterion A; EN 61000-4-3; 2.7 GHz...6 GHz kV / 10 V/m failure criterion A; EN 61000-4-8; 50 / 60 Hz / 30 A/m failure criterion A; EN 61000-4-4 Burst; 4 kV / failure criterion A; EN 61000-4-5 Surge; 2 kV Lx / Ly / failure criterion A; EN 61000-4-5 Surge; 4 kV L / PE / failure criterion A; EN 61000-4-5 Surge; 1 kV + / - / failure criterion A; EN 61000-4-5 Surge; 1 kV + - / PE / failure criterion A; EN 61000-4-5 Surge; 1 kV + - / PE / failure criterion A; EN 61000-4-5 Surge; 1 kV DC-OK / PE / failure criterion A; EN 61000-4-6; 0.15...80 MHz / 20 V failure criterion A; EN 61000-4-11; 0 V up to 1 cycle / failure criterion A; EN 61000-4-11; 40 % of V / 200 ms failure criterion A; EN 61000-4-11; 70 % of V / 500 ms failure criterion A; EN 61000-4-11; 0 V / 5000 ms failure criterion C; VDE 0160; 1550 V / 1.3 ms failure criterion A; EN 55032; Class B; EN 55032; Class B; EN 55011; Class B; EN 61000-3-2; EN 61000-3-3 |
| EN 61000-4-2 CD | 8 kV / failure criterion A |
| EN 61000-4-2 AD | 15 kV / failure criterion A |
| EN 61000-4-3 | 2.7 GHz...6 GHz kV / 10 V/m failure criterion A |
| EN 61000-4-8 | 50 / 60 Hz / 30 A/m failure criterion A |
| EN 61000-4-4 Burst | 4 kV / failure criterion A |
| EN 61000-4-5 Surge | 1 kV DC-OK / PE / failure criterion A |
| EN 61000-4-6 | 0.15...80 MHz / 20 V failure criterion A |
| EN 61000-4-11 | 0 V / 5000 ms failure criterion C |
| VDE 0160 | 1550 V / 1.3 ms failure criterion A |
| EN 55032 | Class B |
| EN 55011 | Class B |
| Continuous shock resistance | IEC 60068-2-27; 30 g 6 ms / 20 g 11 ms |
| IEC 60068-2-27 | 30 g 6 ms / 20 g 11 ms |
| Vibration resistance | IEC 600068-2-6; 2...17.8 Hz ± 1.6mm / 17.8...500 Hz 2 g |
| IEC 600068-2-6 | 2...17.8 Hz ± 1.6mm / 17.8...500 Hz 2 g |
| MTTF[years] [years] | 27 |
Mechanical data
| Weight[g] [g] | 1616.05 |
| Housing | rectangular |
| Type of mounting | backplane mounting |
| Dimensions[mm] [mm] | 199.7 x 178 x 59.5 |
| Materials | housing: aluminium alloy; housing cap: PC; screws: steel bronzed |
Remarks
| Pack quantity | 1 pcs. |
Electrical connection - IO-Link
| Connector | 1 x M12; coding: A; Locking: brass |
Electrical connection - Output voltage
| Connector | 2 x M12; coding: L; Locking: brass |
Electrical connection - power supply
| Connector | 1 x 7/8"; Locking: brass |