Quick facts
| Availability | Confirmed on request |
| Category | AS-Interface power supplies |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can AC1212 be shipped?
AC1212 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up AC1212 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for AC1212 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for AC1212, subject to availability and destination.
Reliably power supply for modules, sensors and actuators High noise immunity and sufficient power reserves for the compensation of current peaks Safe decoupling of interferences from the primary supply Particularly space-saving design Low heating of the control cabinet due to high efficiency
Specifications
Application
| Design | housing for DIN rail mounting |
Electrical data
| Nominal voltage AC[V] [V] | 110 / 230 |
| Nominal frequency AC[Hz] [Hz] | 47...63 |
| Input voltage range AC[V] [V] | 88...132 / 184...264 |
| Max. power-on delay time[ms] [ms] | 500 |
| Output voltage AS-i[V] [V] | 29.5...31.6; (to PELV) |
| Number of output circuits | 2 |
| Output current AS-i[A] [A] | 4 |
| Max. residual ripple[mV] [mV] | 50 |
| External input protection | > 10 A |
| Fuse[A] [A] | 8; (not accessible) |
| Derating[W/K] [W/K] | 1 (60...70 °C) |
| Power loss (nominal voltage 230 V AC / 50 Hz)[W] [W] | 30 |
| Power loss in open-circuit operation[W] [W] | 4 |
| Integrated data decoupling | yes |
Outputs
| Short-circuit protection | yes |
| Overload protection | yes |
| Parallel connection of outputs possible | no |
| Series connection of outputs possible | no |
Operating conditions
| Ambient temperature[°C] [°C] | -10...60 |
| Protection | IP 20 |
Tests / approvals
| EMC | EN 60950/A2 1993; EN 50081-1; EN 61000-6-2 |
| MTTF[years] [years] | 23 |
AS-i classification
| AS-i certificate | 21901 |
Mechanical data
| Weight[g] [g] | 1263.5 |
| Housing | rectangular |
| Type of mounting | mounting on DIN rail; (TH35 (EN 60715)) |
| Dimensions[mm] [mm] | 134 x 120 x 118.5 |
| Materials | aluminium |
Displays / operating elements
| Display | function; 2 x LED, green |
| function | 2 x LED, green |
Remarks
| Pack quantity | 1 pcs. |
Electrical connection
| terminals | ...2.5 mm² |